KEYPAD AND DISPLAY
GEK-106273L
MIF Digital Feeder Protection
8-21
Mnemonics appearing in the ADVANCED SETTINGS group, only for OPTION 2 models:
I^2
I
2
counter
I^2
MAX
Alarm level for I
2
0 – 999.0 kA2
Step: 0.001
CLP
Cold
load
pickup
CLP ENABLE
Permission CLP
Y (YES) / N (NO)
T IN
Pickup
timer
setting
1 – 60 seg.
Step: 0.001
T OUT
Drop out timer setting
1 – 60 seg.
Step: 0.001
K 5OP
Multiplier for 50P tap
1 – 5
Step: 0.01
K 51P
Multiplier for 51P tap
1 – 5
Step: 0.01
BF
Breaker
failure
to
open
BF ENABLE
Permission BF
Y (YES) / N (NO)
BF TIME
Breaker failure to open time
50 – 999 msec.
Step: 1 msec.
Summary of Contents for GEK-106273L
Page 19: ...GETTING STARTED 1 12 MIF Digital Feeder Protection GEK 106273L ...
Page 95: ...SETTINGS 5 38 MIF Digital Feeder Protection GEK 106273L ...
Page 101: ...I O CONFIGURATION 6 44 MIF Digital Feeder Protection GEK 106273L ...
Page 127: ...KEYPAD AND DISPLAY 8 26 MIF Digital Feeder Protection GEK 106273L ...
Page 147: ...INSTALLATION AND MAINTENANCE 10 2 MIF Digital Feeder Protection GEK 106273L ...
Page 199: ...ANNEX 5 HARMONIC FILTERING 15 4 MIF Digital Feeder Protection GEK 106273L ...