ANNEX 3 MODBUS MEMORY MAP
13-6
MIF Digital Feeder Protection
GEK-106273L
2. SETTING CHANGE
Request:
ADDRESS FUNCTION BEGINNING #REGS #BYTES
01 10 0118
0008
10
DATA0
DATA1
DATA2
DATA3
DATA4
5052
5545
4241
0049
4341
DATA5
DATA6
DATA7
CRC
5449
4F4E
2020
3AE1
Data0 => 5052 (“P””R”)
Data1 => 5545 (“U””E”)
Data2 => 4241 (“B””A”)
Data3 => 00xx (End of text. The rest of characters are not considered)
Reply:
ADDRESS FUNCTION BEGINNING #REGS CRC
01 10
0118
0008
4034
SETTING CHANGE CONFIRMATION (LIKE A COMMAND):
Request
:
ADDRESS FUNCTION BEGINNING #REGS #BYTES DATA0 DATA1 DATA2 CRC
01
10
0000
0003 06 0200 0100 0000
E69E
Reply
:
ADDRESS FUNCTION BEGINNING #REGS CRC
01 10
0000
00
03
8008