RELAY COMMISSIONING
9-16
MIF Digital Feeder Protection
GEK-106273L
ENERVISTA MII
SETUP
HMI
USER
VALUE
RANGE
STEP
Gnd IOC Low Set Table 2
50NL Function (Table
2)
F50NL T2
50NL Permission to Trip
50NL Trip Permission
TRIP 50NL T2
Y/N
NA
50NL Tap / Pickup (1/5 A
ground)
50NL Pickup T2
TAP 50NL T2
0.1 – 30 In (Gnd) 0.1 In (G)
50NL Tap / Pickup
(sensitive ground)
50NL Pickup T2
TAP 50NL T2
0.005-0.12 A
0.001 A
50NL Time Delay
50NL Time Delay T2
TIME 50NL T2
0 – 600.00 s.
0.01 s.
Thermal Image Table 2
49 Function (Table 2)
F49 T2
Permission to Trip
49 Trip Permission T2
TRIP 49 T2
Y/N
NA
49 Tap / Pickup
49 Pickup T2
TAP 49 T2
0.1 – 2.4 In (Ph)
0.01 In
Overload Percent Alarm
49 Alarm Level T2
ALARM 49 T2
70% – 100% ITH
Heating Time Constant
τ
1
T1 T2
T1 T2
3 – 600 min.
1 min.
Cooling Time Constant
τ
2
T2 T2
T2 T2
1– 6 times
τ
1
1
USER’S CURVE
A A
A
0-125
0.001
B B
B
0-3
0.001
P P
P
0-3
0.001
Q Q
Q
0-2
0.001
K K
K
0-1.999
0.001
Summary of Contents for GEK-106273L
Page 19: ...GETTING STARTED 1 12 MIF Digital Feeder Protection GEK 106273L ...
Page 95: ...SETTINGS 5 38 MIF Digital Feeder Protection GEK 106273L ...
Page 101: ...I O CONFIGURATION 6 44 MIF Digital Feeder Protection GEK 106273L ...
Page 127: ...KEYPAD AND DISPLAY 8 26 MIF Digital Feeder Protection GEK 106273L ...
Page 147: ...INSTALLATION AND MAINTENANCE 10 2 MIF Digital Feeder Protection GEK 106273L ...
Page 199: ...ANNEX 5 HARMONIC FILTERING 15 4 MIF Digital Feeder Protection GEK 106273L ...