58
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – COMMUNICATIONS GUIDE
MODBUS MEMORY MAP
CHAPTER 2: MODBUS COMMUNICATION
2545
Breaker 1 Block Open Cmd
0 to 65535
---
1
F300
0
2546
Breaker 1 Ext Close Cmd
0 to 65535
---
1
F300
0
2547
Breaker 1 AR Close Supv
0 to 65535
---
1
F300
0
2548
Breaker 1 Block Close Cmd
0 to 65535
---
1
F300
0
2549
Breaker 1 BKR in Local
0 to 65535
---
1
F300
0
254A
Breaker 1 Indication Mode
0 to 1
---
1
F157
0 (3-Pole)
254B
Breaker 1 A/3P Closed Status
0 to 65535
---
1
F300
0
254C
Breaker 1 A/3P Opened Status
0 to 65535
---
1
F300
0
254D
Breaker 1 B Closed Status
0 to 65535
---
1
F300
0
254E
Breaker 1 B Opened Status
0 to 65535
---
1
F300
0
254F
Breaker 1 C Closed Status
0 to 65535
---
1
F300
0
2550
Breaker 1 C Opened Status
0 to 65535
---
1
F300
0
2551
Breaker 1 Toperate
0 to 2
s
0.001
F001
70
2552
Breaker 1 Tdiscrep
0 to 2
s
0.001
F001
70
2553
Breaker 1 Reset Counter
0 to 65535
---
1
F300
0
2554
Breaker 1 Events
0 to 1
---
1
F102
1 (Enabled)
2555
...Repeated for Breaker 2
257A
...Repeated for Breaker 3
259F
...Repeated for Breaker 4
25C4
...Repeated for Breaker 5
25E9
...Repeated for Breaker 6
Breaker Control (Read/Write Setting) (6 Modules)
2610
Breaker 1 Cntrl Function
0 to 1
---
1
F102
0 (Disabled)
2611
Breaker 1 Cntrl PB Control
0 to 1
---
1
F102
1 (Enabled)
2612
Breaker 1 Cntrl Local Control
0 to 65535
---
1
F300
0
2613
Breaker 1 Cntrl Remote Control
0 to 65535
---
1
F300
0
2614
Breaker 1 Cntrl Tselect
0 to 30
s
0.1
F001
100
2615
Breaker 1 Cntrl Auto Close
0 to 65535
---
1
F300
0
2616
Breaker 1 Cntrl Auto Open
0 to 65535
---
1
F300
0
2617
Breaker 1 Cntrl Texec
0 to 10
s
0.1
F001
100
2618
Breaker 1 Cntrl Control Bypass
0 to 1
---
1
F102
0 (Disabled)
2619
Breaker 1 Cntrl Auto Bypass
0 to 65535
---
1
F300
0
261A
Breaker 1 Cntrl Tbypass
0 to 30
s
0.1
F001
100
261B
Breaker 1 Cntrl Events
0 to 1
---
1
F102
1 (Enabled)
261C
...Repeated for Breaker 2
2628
...Repeated for Breaker 3
2634
...Repeated for Breaker 4
2640
...Repeated for Breaker 5
264C
...Repeated for Breaker 6
Breaker Interlock (Read/Write Setting) (6 Modules)
2660
Breaker 1 Interlock Function
0 to 1
---
1
F102
0 (Disabled)
2661
Breaker 1 Interlock Tagging
0 to 1
---
1
F102
0 (Disabled)
2662
Breaker 1 Status Supv
0 to 1
---
1
F102
0 (Disabled)
2663
Breaker 1 Interlock Close Interlock 1
0 to 65535
---
1
F300
0
2664
Breaker 1 Interlock Close Interlock 2
0 to 65535
---
1
F300
0
2665
Breaker 1 Interlock Close Interlock 3
0 to 65535
---
1
F300
0
2666
Breaker 1 Interlock Sync Permissive
0 to 65535
---
1
F300
0
Address Description
Range
Units
Step