CHAPTER 2: MODBUS COMMUNICATION
MODBUS MEMORY MAP
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – COMMUNICATIONS GUIDE
87
5D10
...Repeated for Ground Time Overcurrent 2
5D20
...Repeated for Ground Time Overcurrent 3
5D30
...Repeated for Ground Time Overcurrent 4
5D40
...Repeated for Ground Time Overcurrent 5
5D50
...Repeated for Ground Time Overcurrent 6
Ground Instantaneous Overcurrent (IOC) (Read/Write Grouped Setting) (12 Modules)
5E00
Ground Instantaneous Overcurrent 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
5E01
Ground Instantaneous Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
5E02
Ground Instantaneous Overcurrent 1 Pickup
0 to 30
pu
0.001
F001
1000
5E03
Ground Instantaneous Overcurrent 1 Delay
0 to 600
s
0.01
F001
0
5E04
Ground Instantaneous Overcurrent 1 Reset Delay
0 to 600
s
0.01
F001
0
5E05
Ground Instantaneous Overcurrent 1 Block
0 to 65535
---
1
F300
0
5E07
Ground Instantaneous Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
5E08
Ground Instantaneous Overcurrent 1 Reserved (8
items)
0 to 1
---
1
F001
0
5E10
...Repeated for Ground Instantaneous Overcurrent 2
5E20
...Repeated for Ground Instantaneous Overcurrent 3
5E30
...Repeated for Ground Instantaneous Overcurrent 4
5E40
...Repeated for Ground Instantaneous Overcurrent 5
5E50
...Repeated for Ground Instantaneous Overcurrent 6
5E60
...Repeated for Ground Instantaneous Overcurrent 7
5E70
...Repeated for Ground Instantaneous Overcurrent 8
5E80
...Repeated for Ground Instantaneous Overcurrent 9
5E90
...Repeated for Ground Instantaneous Overcurrent 10
5EA0
...Repeated for Ground Instantaneous Overcurrent 11
5EB0
...Repeated for Ground Instantaneous Overcurrent 12
Setting Groups (Read/Write Setting)
5F80
Communications Group
0 to 5
---
1
F001
0
5F81
Setting Groups Block
0 to 65535
---
1
F300
0
5F82
Groups Activate On (5 items)
0 to 65535
---
1
F300
0
5F89
Setting Group Function
0 to 1
---
1
F102
0 (Disabled)
5F8A
Setting Group Events
0 to 1
---
1
F102
0 (Disabled)
Setting Groups (Read Only Non-Volatile)
5F8B
Current Setting Group
0 to 5
---
1
F001
0
Wattmetric Ground Fault (Read/Write Grouped Setting) (2 Modules)
6050
Wattmetric Ground Fault 1 Function
0 to 1
---
1
F102
0 (Disabled)
6051
Wattmetric Ground Fault 1 Source
0 to 5
---
1
F167
0 (SRC 1)
6052
Wattmetric Ground Fault 1 Voltage
0 to 1
---
1
F234
0 (Calculated
VN)
6053
Wattmetric Ground Fault 1 Overvoltage Pickup
0.02 to 1.1
pu
0.01
F001
20
6054
Wattmetric Ground Fault 1 Current
0 to 1
---
1
F235
0 (Calculated
IN)
6055
Wattmetric Ground Fault 1 Overcurrent Pickup
0.002 to 30.000
pu
0.001
F001
60
6056
Wattmetric Ground Fault 1 Overcurrent Pickup Delay 0 to 600
s
0.01
F001
20
6057
Wattmetric Ground Fault 1 Power Pickup
0.001 to 1.2
pu
0.001
F001
100
6058
Wattmetric Ground Fault 1 ECA
0 to 360
° Lag
1
F001
0
6059
Wattmetric Ground Fault 1 Power Pickup Delay
0 to 600
s
0.01
F001
20
Address Description
Range
Units
Step
Format Default