90
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – COMMUNICATIONS GUIDE
MODBUS MEMORY MAP
CHAPTER 2: MODBUS COMMUNICATION
6703
Load Encroachment Reach
0.02 to 250
ohms
0.01
F001
100
6704
Load Encroachment Angle
5 to 50
degrees 1
F001
30
6705
Load Encroachment Pickup Delay
0 to 65.535
s
0.001
F001
0
6706
Load Encroachment Reset Delay
0 to 65.535
s
0.001
F001
0
6707
Load Encroachment Block
0 to 65535
---
1
F300
0
6709
Load Encroachment Events
0 to 1
---
1
F102
0 (Disabled)
670A
Reserved (6 items)
0 to 65535
---
1
F001
0
Trip Output (Read/Write Setting)
6800
Trip Mode
0 to 2
---
1
F195
0 (Disabled)
6801
Trip 3-Pole Input1
0 to 65535
---
1
F300
0
6802
Trip 3-Pole Input2
0 to 65535
---
1
F300
0
6803
Trip 3-Pole Input3
0 to 65535
---
1
F300
0
6804
Trip 3-Pole Input4
0 to 65535
---
1
F300
0
6805
Trip 3-Pole Input5
0 to 65535
---
1
F300
0
6806
Trip 3-Pole Input6
0 to 65535
---
1
F300
0
6807
Trip 1-Pole Input1
0 to 65535
---
1
F300
0
6808
Trip 1-Pole Input2
0 to 65535
---
1
F300
0
6809
Trip 1-Pole Input3
0 to 65535
---
1
F300
0
680A
Trip 1-Pole Input4
0 to 65535
---
1
F300
0
680B
Trip 1-Pole Input5
0 to 65535
---
1
F300
0
680C
Trip 1-Pole Input6
0 to 65535
---
1
F300
0
680D
Trip Reclose Input1
0 to 65535
---
1
F300
0
680E
Trip Reclose Input2
0 to 65535
---
1
F300
0
680F
Trip Reclose Input3
0 to 65535
---
1
F300
0
6810
Trip Reclose Input4
0 to 65535
---
1
F300
0
6811
Trip Reclose Input5
0 to 65535
---
1
F300
0
6812
Trip Reclose Input6
0 to 65535
---
1
F300
0
6813
Trip Force 3-Pole
0 to 65535
---
1
F300
0
6814
Trip Pilot Priority
0 to 65.535
s
0.001
F001
0
6815
Breaker Phase A Open
0 to 65535
---
1
F300
0
6816
Breaker Phase B Open
0 to 65535
---
1
F300
0
6817
Breaker Phase C Open
0 to 65535
---
1
F300
0
6818
Trip Events
0 to 1
---
1
F102
0 (Disabled)
6819
Reverse Fault Operand
0 to 65535
---
1
F300
0
681A
Trip Delay On Evolving Faults
0 to 65.535
s
0.001
F001
0
681B
Reserved (5 items)
0 to 1
---
1
F001
0
Open Pole Detect (1P) (Read/Write Setting)
6820
Open Pole Function
0 to 1
---
1
F102
0 (Disabled)
6821
Open Pole Block
0 to 65535
---
1
F300
0
6822
Open Pole Voltage Supervision
0 to 1
---
1
F102
0 (Disabled)
6823
Open Pole Current Pickup
0 to 30
pu
0.001
F001
50
6825
Open Pole Events
0 to 1
---
1
F102
0 (Disabled)
6826
Open Pole Line XC0
300 to 9999.9
ohms
0.1
F003
99999
6828
Open Pole Line XC1
300 to 9999.9
ohms
0.1
F003
99999
682A
Open Pole Remote Current Pickup
0 to 30
pu
0.001
F001
50
682B
Reserved (5 items)
0 to 1
---
1
F001
0
Pilot DUTT (1P) (Read/Write Setting)
Address Description
Range
Units
Step
Format Default