LINE DISTANCE PROTECTION SYSTEM – COMMUNICATIONS GUIDE
MODBUS MEMORY MAP
CHAPTER 2: MODBUS COMMUNICATION
605A
Wattmetric Ground Fault 1 Curve
0 to 5
---
1
F236
0 (Definite
Time)
605B
Wattmetric Ground Fault 1 Multiplier
0.01 to 2
s
0.01
F001
100
605C
Wattmetric Ground Fault 1 Block
0 to 65535
---
1
F300
0
605D
Wattmetric Ground Fault 1 Events
0 to 1
---
1
F102
0 (Disabled)
605E
Wattmetric Ground Fault 1 Reference Power
0.001 to 1.2
pu
0.001
F001
500
605F
Wattmetric Ground Fault x Reserved (9 items)
0 to 1
---
1
F001
0
6068
...Repeated for Wattmetric Ground Fault 2
Negative Sequence Time Overcurrent (TOC) (Read/Write Grouped Setting) (2 Modules)
6300
Negative Sequence Time Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
6301
Negative Sequence Time Overcurrent 1 Signal Source 0 to 5
---
1
F167
0 (SRC 1)
6302
Negative Sequence Time Overcurrent 1 Pickup
0 to 30
pu
0.001
F001
1000
6303
Negative Sequence Time Overcurrent 1 Curve
0 to 16
---
1
F103
0 (IEEE Mod
Inv)
6304
Negative Sequence Time Overcurrent 1 Multiplier
0 to 600
---
0.01
F001
100
6305
Negative Sequence Time Overcurrent 1 Reset
0 to 1
---
1
F104
0
(Instantaneou
s)
6306
Negative Sequence Time Overcurrent 1 Block
0 to 65535
---
1
F300
0
6308
Negative Sequence Time Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
6309
Negative Sequence Time Overcurrent 1 Reserved (7
items)
0 to 1
---
1
F001
0
6310
...Repeated for Negative Sequence Time Overcurrent
2
Negative Sequence Instantaneous Overcurrent (Read/Write Grouped Setting) (2 Modules)
6400
Negative Sequence Instantaneous OC 1 Function
0 to 1
---
1
F102
0 (Disabled)
6401
Negative Sequence Instantaneous OC 1 Signal
Source
0 to 5
---
1
F167
0 (SRC 1)
6402
Negative Sequence Instantaneous Overcurrent 1
Pickup
0 to 30
pu
0.001
F001
1000
6403
Negative Sequence Instantaneous Overcurrent 1
Delay
0 to 600
s
0.01
F001
0
6404
Negative Sequence Instantaneous OC 1 Reset Delay 0 to 600
s
0.01
F001
0
6405
Negative Sequence Instantaneous Overcurrent 1
Block
0 to 65535
---
1
F300
0
6407
Negative Sequence Instantaneous Overcurrent 1
Events
0 to 1
---
1
F102
0 (Disabled)
6408
Negative Sequence Instantaneous Overcurrent
Reserved (8 items)
0 to 1
---
1
F001
0
6410
...Repeated for Negative Sequence Instantaneous OC
2
Negative Sequence Overvoltage (Read/Write Grouped Setting) (2 Modules)
64A0
Negative Sequence Overvoltage 1 Function
0 to 1
---
1
F102
0 (Disabled)
64A1
Negative Sequence Overvoltage 1 Source
0 to 5
---
1
F167
0 (SRC 1)
64A2
Negative Sequence Overvoltage 1 Pickup
0 to 1.25
pu
0.001
F001
300
64A3
Negative Sequence Overvoltage 1 Pickup Delay
0 to 600
s
0.01
F001
50
64A4
Negative Sequence Overvoltage 1 Reset Delay
0 to 600
s
0.01
F001
50
64A5
Negative Sequence Overvoltage 1 Block
0 to 65535
---
1
F300
0
64A7
Negative Sequence Overvoltage 1 Events
0 to 1
---
1
F102
0 (Disabled)
64A8
...Repeated for Negative Sequence Overvoltage 2
Overfrequency (Read/Write Setting) (4 Modules)
Address Description
Range
Units
Step
Format Default