198
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – COMMUNICATIONS GUIDE
DNP DEVICE PROFILE
CHAPTER 3: DNP COMMUNICATION
–
Analog input changes (object 32)
–
Analog deadbands (object 34)
–
Time and date (object 50)
–
Time delay fine (object 52)
–
Class 0, 1, 2, and 3 data (object 60)
–
File transfer (object 70)
–
Internal indications (object 80)
•
Maximum data link frame size (octets):
–
Transmitted — 292
–
Received — 292
•
Maximum application fragment size (octets):
–
Transmitted — Configurable up to 2048
–
Received — 2048
•
Maximum data link re-tries — None
•
Maximum application layer re-tries — None
•
Requires data link layer confirmation — Never
•
Requires application layer confirmation — When reporting event data, when sending
multi-fragment responses
•
Timeouts while waiting for:
–
Data link confirm — None
–
Complete application fragment — None
–
Application confirm — Fixed at 10 seconds
–
Complete application response — None
•
Others:
–
Transmission delay — No intentional delay
–
Need time interval — Configurable (default is 24 hours)
–
Select/operate arm timeout — 10 seconds
–
Binary input change scanning period — 16 times per power system cycle
–
Analog input change scanning period — 500 ms
–
Counter change scanning period — 500 ms
–
Frozen counter event scanning period — 500 ms
–
Unsolicited response notification delay —100 ms
–
Unsolicited response retry delay — Configurable from 0 to 60 seconds
•
Sends/executes control operations:
–
Write binary outputs — Never
–
Select/operate — Always
–
Direct operate — Always
–
Direct operate – no acknowledge — Always
–
Count
>
1 — Never
–
Pulse on — Sometimes
–
Pulse off — Sometimes
–
Latch on — Sometimes
–
Latch off — Sometimes
–
Queue — Never
–
Clear queue — Never