94
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – COMMUNICATIONS GUIDE
MODBUS MEMORY MAP
CHAPTER 2: MODBUS COMMUNICATION
68D0
Directional Comparison Unblocking Rx1
0 to 65535
---
1
F300
0
68D1
Directional Comparison Unblocking LOG1
0 to 65535
---
1
F300
0
68D2
Directional Comparison Unblocking Rx2
0 to 65535
---
1
F300
0
68D3
Directional Comparison Unblocking LOG2
0 to 65535
---
1
F300
0
68D4
Directional Comparison Unblocking Rx3
0 to 65535
---
1
F300
0
68D5
Directional Comparison Unblocking LOG3
0 to 65535
---
1
F300
0
68D6
Directional Comparison Unblocking Rx4
0 to 65535
---
1
F300
0
68D7
Directional Comparison Unblocking LOG4
0 to 65535
---
1
F300
0
68D8
Directional Comparison Unblocking Event
0 to 1
--
1
F102
0 (Disabled)
68D9
Reserved (6 items)
0 to 1
--
1
F001
0
Phase Undervoltage (Read/Write Grouped Setting) (2 Modules)
7000
Phase Undervoltage 1 Function
0 to 1
---
1
F102
0 (Disabled)
7001
Phase Undervoltage 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
7002
Phase Undervoltage 1 Pickup
0 to 1.1
pu
0.001
F001
1000
7003
Phase Undervoltage 1 Curve
0 to 1
---
1
F111
0 (Definite
Time)
7004
Phase Undervoltage 1 Delay
0 to 600
s
0.01
F001
100
7005
Phase Undervoltage 1 Minimum Voltage
0 to 3
pu
0.001
F001
100
7006
Phase Undervoltage 1 Block
0 to 65535
---
1
F300
0
7008
Phase Undervoltage 1 Events
0 to 1
---
1
F102
0 (Disabled)
7009
Phase Undervoltage 1 Measurement Mode
0 to 1
---
1
F186
0 (Phase to
Ground)
700A
Phase Undervoltage 1 Reserved (6 items)
0 to 1
---
1
F001
0
7010
...Repeated for Phase Undervoltage 2
Phase Overvoltage (Read/Write Grouped Setting) (2 Modules)
7040
Phase Overvoltage 1 Function
0 to 1
---
1
F102
0 (Disabled)
7041
Phase Overvoltage 1 Source
0 to 5
---
1
F167
0 (SRC 1)
7042
Phase Overvoltage 1 Pickup
0 to 3
pu
0.001
F001
1000
7043
Phase Overvoltage 1 Delay
0 to 600
s
0.01
F001
100
7044
Phase Overvoltage 1 Reset Delay
0 to 600
s
0.01
F001
100
7045
Phase Overvoltage 1 Block
0 to 65535
---
1
F300
0
7047
Phase Overvoltage 1 Events
0 to 1
---
1
F102
0 (Disabled)
7048
Phase Overvoltage 1 Reserved (8 items)
0 to 1
---
1
F001
0
7050
...Repeated for Phase Overvoltage 2
Distance (Read/Write Grouped Setting)
7060
Distance Signal Source
0 to 5
---
1
F167
0 (SRC 1)
7061
Memory Duration
5 to 25
cycles
1
F001
10
7062
Force Self-Polarization
0 to 65535
---
1
F300
0
7063
Force Memory Polarization
0 to 65535
---
1
F300
0
7064
Distance CVT Filter Function
0 to 1
---
1
F102
0 (Disabled)
7065
Distance CVT Filter T1
0.25 to 10
ms
0.01
F001
100
7066
Distance CVT Filter T2
0.25 to 10
ms
0.01
F001
100
7067
Distance CVT Filter Tx
0.25 to 10
ms
0.01
F001
100
Phase Distance (Read/Write Grouped Setting) (5 Modules)
7070
Phase Distance Zone 1 Function
0 to 1
---
1
F102
0 (Disabled)
7071
Phase Distance Zone 1 Current Supervision
0.05 to 30
pu
0.001
F001
200
7072
Phase Distance Zone 1 Reach
0.02 to 500
ohms
0.01
F001
200
Address Description
Range
Units
Step
Format Default