CHAPTER 6: USING THE D.20 RIO
CONFIGURING SINGLE AND REDUNDANT D.20 RIOS
D.20 RIO - HARDWARE USER’S MANUAL
GE Information
55
4.
Connect to the D400 HMI and execute the following steps.
4.1.
In the Connection Configuration screen, add Network connections and select
D.20 Network Client
from the drop down menu.
4.2.
Add the D.20 RIO device and click the
Retrieve D.20 RIO Configuration
tab.
To ensure that the service starts automatically, select the
Block Settings
>
Auto-start
option, and select
Enable on Startup
in the D.20 RIO device list table
for each device you add to the D400
4.3.
Enter the IP address, User Name and Password of the primary D.20 RIO and
click
Download
. The default protocol is HTTP for retrieving the D.20 RIO
configuration; however if the user configures HTTPS in D.20 RIO then the
protocol for retrieving the D.20 RIO configuration should be HTTPS.
4.4.
If the error message:
Max users logged in for user
appears in the D400 HMI,
then close all open D.20 RIO HMI sessions and try to download the D.20 RIO
configuration again using the
Retrieve D.20 RIO Configuration
tab of the D400
HMI.
4.5.
Once the primary D.20 RIO configuration download is successful, a pop-up
message appears: Found Redundant RIO, NTP Time Synchronization and
Configuration should be done properly.
4.6.
Click
OK
.
Result: Another pop-up window appears for the secondary D.20 RIO with the
default username/password (supervisor/super123$) of the secondary D.20 RIO.
NOTE
If another username/password is configured for secondary D.20 RIO, then edit
the username and password accordingly.
4.7.
If the error message:
Max users logged in for user
appears, then close the
current active secondary D.20 RIO HMI sessions and repeat the steps 4.3. to 4.6.
4.8.
Click the
Setup
button to download the configuration to the secondary D.20
RIO.
Result: All related configuration data is now synchronized between the primary
and secondary D.20 RIOs.
4.9.
Save and commit the configuration in the D400 HMI.
Verifying D.20 RIO redundancy states
The D.20 RIO redundancy states can be verified from either the:
•
D400, or
•
D.20 RIO command line.
To verify D.20 RIO redundancy states from the D400:
•
Use the information in Table 17 to create Analog Input (AI) text enumeration mapping
in the D400 for D.20 RIO analog points indicating D.20 RIO states.
Table 17: D.20 RIO redundancy states
AI Point Value
AI Text Enumeration
0
Wait
1
Active Non-Redundant
2
Active
4
Standby
8
Failed