5-116
B90 Low Impedance Bus Differential System
GE Multilin
5.5 GROUPED ELEMENTS
5 SETTINGS
5
Figure 5–53: END FAULT PROTECTION LOGIC
SETTING
EFP 1 FUNCTION:
Disabled = 0
Enabled = 1
SETTING
EFP 1 CT:
Current Magnitude, |I|
FLEXLOGIC OPERANDS
EFP 1 OP
SETTING
B90 FUNCTION:
Logic = 0
Protection = 1
AN
D
SETTING
EFP 1 BLOCK:
Off = 0
EFP 1 DPO
EFP PKP
SETTINGS
EFP 1 BRK DELAY:
t
PKP
0
SETTING
| I | > PICKUP
RUN
EFP 1 PICKUP:
SETTING
EFP 1 MANUAL CLOSE:
Off = 0
SETTING
EFP 1 BREAKER OPEN:
Off = 0
AN
D
SETTING
EFP 1 PICKUP DELAY:
t
PKP
0
836004A1.vsd