5-56
B90 Low Impedance Bus Differential System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
The user-programmable pushbutton logic is shown below.
Figure 5–12: USER-PROGRAMMABLE PUSHBUTTON LOGIC (Sheet 1 of 2)
S
R
Non-volatile latch
Latch
OR
OR
OR
OR
OR
OR
AND
SETTING
= Enabled
= Latched
Function
= Self-Reset
SETTING
Off = 0
Remote Lock
SETTING
Off = 0
Local Lock
SETTING
Off = 0
Set
SETTING
Off = 0
Reset
SETTING
= Enabled
= Disabled
Autoreset Function
FLEXLOGIC OPERAND
PUSHBUTTON 1 ON
FLEXLOGIC OPERAND
PUSHBUTTON 1 OFF
TIMER
200 ms
0
AND
AND
AND
AND
AND
TIMER
50 ms
0
TIMER
50 ms
0
SETTING
Autoreset Delay
T
PKP
0
TIMER
200 ms
0
AND
AND
SETTING
Drop-Out Timer
T
RST
0
PUSHBUTTON ON
To user-programmable
pushbuttons logic
sheet 2, 842024A2
LATCHED
LATCHED/SELF-RESET
To user-programmable
pushbuttons logic
sheet 2, 842024A2
842021A3.CDR
SETTING
Hold
T
PKP
0