Number of elements:
48
Operating signal:
any FlexLogic operand
Pickup delay:
0.000 to 999999.999 s in steps of 0.001
Dropout delay:
0.000 to 999999.999 s in steps of 0.001
Timing accuracy:
±3% or ±4 ms, whichever is greater
2.2.3 MONITORING
OSCILLOGRAPHY
Maximum records:
64
Sampling rate:
64 samples per power cycle
Triggers:
any element pickup, dropout, or operate;
digital input change of state; digital out-
put change of state; FlexLogic equation
Data:
AC input channels; element state; digital
input state; digital output state
Data storage:
in non-volatile memory
EVENT RECORDER
Capacity:
1024 events
Time-tag:
to 1 microsecond
Triggers:
any element pickup, dropout, or operate;
digital input change of state; digital out-
put change of state; self-test events
Data storage:
in non-volatile memory
USER-PROGRAMMABLE FAULT REPORT
Number of elements:
2
Pre-fault trigger:
any FlexLogic operand
Fault trigger:
any FlexLogic operand
Recorder quantities:
32 (any FlexAnalog
TM
value)
Summary of Contents for B90 UR Series
Page 316: ...A 4 B90 Low Impedance Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 406: ...B 90 B90 Low Impedance Bus Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 436: ...C 30 B90 Low Impedance Bus Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 446: ...D 10 B90 Low Impedance Bus Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...