The Supervisory menu settings are available for Supervisor role only or if the Supervisor role is disabled then for the
Administrator role only.
Figure 5–2: SUPERVISORY PANEL
Local Authentication:
When enabled (i.e., "Yes" is selected) Local Authentication with roles is enabled. When this setting
is disabled the UR only authenticates to the AAA server (Radius). This means the front communications port is disabled as
well. The setting is enabled by default.
Bypass Access:
Enabling this setting allows 502 ethernet sessions to the relay. The serial ports (RS232 and RS485) allow
settings write. No passwords or roles are required when in this mode. When disabled, everything goes back to normal. This
setting has no effect on the front panel and it continues to support Role Based Access Control (RBAC).
Lock Relay:
This setting uses a Boolean value (Enable/Disable) to indicate if the device accepts setting changes and
whether the device can receive a firmware upgrade. This setting can be changed only by the Supervisor role, if it is enabled
or by the Administrator if the Supervisor role is disabled. The Supervisor role enables this setting for the relay to start
accepting setting changes or command changes or firmware upgrade. After all the setting changes are applied or com-
mands executed, the Supervisor disables to lock setting changes.
Example:
If this setting is "Yes" and an attempt is made to change settings or upgrade the firmware, the UR device denies
the setting changes and denies upgrading the firmware. If this setting is "No", the UR device accepts setting changes and
firmware upgrade.
This role is disabled by default.
MODE
SERIAL (RS232 & RS485)
502 ETHERNET
SSH ETHERNET
Bypass Access = Disable
Local Authentication
and Role Based Access
Control (RBAC)
and passwords in clear
Read only
Local/Remote Authentication
and Role Based Access Control (RBAC)
and passwords encrypted
Bypass Access = Enable
No Role Based Access Control
(RBAC)
and no passwords
No Role Based Access
Control (RBAC)
and no passwords
Local/Remote Authentication
and Role Based Access Control (RBAC)
and passwords encrypted
Summary of Contents for B90 UR Series
Page 316: ...A 4 B90 Low Impedance Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 406: ...B 90 B90 Low Impedance Bus Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 436: ...C 30 B90 Low Impedance Bus Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 446: ...D 10 B90 Low Impedance Bus Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...