5-98
B90 Low Impedance Bus Differential System
GE Multilin
5.5 GROUPED ELEMENTS
5 SETTINGS
5
5.5.4 BREAKER FAILURE
PATH: SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
BREAKER FAILURE 1(24)
BREAKER FAILURE
BREAKER FAILURE
CURRENT SUPV 1
MESSAGE
BF1 CURRENT SUPV
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
BF1 CT:
F1
Range: Available current channels
MESSAGE
BF1 AMP SUPV
PICKUP: 1.050 pu
Range: 0.001 to 30.000 pu in steps of 0.001
MESSAGE
BF1 AMP HISET
PICKUP: 1.050 pu
Range: 0.001 to 30.000 pu in steps of 0.001
MESSAGE
BF1 AMP LOSET
PICKUP: 1.050 pu
Range: 0.001 to 30.000 pu in steps of 0.001
BREAKER FAILURE 1
MESSAGE
BF1 FUNCTION:
Disabled
Range: Disabled, Enabled
MESSAGE
BF1 INITIATE:
Off
Range: FlexLogic™ operand
MESSAGE
BF1 USE AMP SUPV:
Yes
Range: Yes, No
MESSAGE
BF1 USE SEAL-IN:
Yes
Range: Yes, No
MESSAGE
BF1 AMP SUPV OP A:
Off
Range: FlexLogic™ operand
MESSAGE
BF1 AMP SUPV OP B:
Off
Range: FlexLogic™ operand
MESSAGE
BF1 AMP SUPV OP C:
Off
Range: FlexLogic™ operand
MESSAGE
BF1 USE TIMER 1:
Yes
Range: Yes, No
MESSAGE
BF1 TIMER 1 PICKUP
DELAY: 0.000 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
BF1 USE TIMER 2:
Yes
Range: Yes, No
MESSAGE
BF1 TIMER 2 PICKUP
DELAY: 0.000 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
BF1 USE TIMER 3:
Yes
Range: Yes, No
Summary of Contents for B90 UR Series
Page 316: ...A 4 B90 Low Impedance Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 406: ...B 90 B90 Low Impedance Bus Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 436: ...C 30 B90 Low Impedance Bus Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 446: ...D 10 B90 Low Impedance Bus Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...