CHAPTER 4: SETPOINTS
INPUTS
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
4–117
Inputs
Figure 4-34: Inputs Display Hierarchy
Contact Inputs
The 845 relay is equipped with a number of Contact Inputs, depending on the Order Code,
which can be used to provide a variety of functions such as for circuit breaker control,
external trips, blocking of protection elements, etc. Contact inputs accept wet and dry
input signals. A wet type contact input signal requires an external DC voltage source. A dry
type contact input signal uses an internal DC voltage source. Depending on the DC source
level, the voltage threshold (17V, 33V, 84V, 166V) can be selected. The Contact Inputs can be
located on the HV I/O and Arc Flash cards located on slots ‘B’ or ‘C’ or ‘F’ or ‘G’ or ‘H’ or all.
NOTE
NOTE:
The maximum load current that can be delivered by the relay +24 V wetting voltage supply
is 100 mA. When the in24 V supply is used, the current limitations of the 24V supply
must be considered.
The Contact Inputs are either open or closed with a programmable debounce time to
prevent false operation from induced voltage. The debounce time is adjustable by the user
per manufacturer specifications.
A raw status is scanned for all Contact Inputs synchronously at the constant rate of one
protection pass (1/8 cycle) as shown in the figure below. The DC input voltage is compared
to a user-settable threshold. A new Contact Input state must be maintained for a user
settable debounce time in order for the relay to validate the new contact state. In the
figure below, the debounce time is set at 2.5 ms; thus the 3rd sample in a row validates the
Level 1
Level 2
Level 3
Level 4
Setpoints
Device
System
Inputs
Outputs
Protection
Monitoring
Control
FlexLogic
Data Capture
Virtual Inputs
Contact Inputs
*
IEC 61850 is selected in the order code
Remote Inputs is only available when
Analog Inputs
Testing
Remote Inputs*
Summary of Contents for 845
Page 10: ...VIII 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 219: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 91 ...
Page 221: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 93 ...
Page 222: ...4 94 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL SYSTEM CHAPTER 4 SETPOINTS ...
Page 223: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 95 ...
Page 224: ...4 96 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL SYSTEM CHAPTER 4 SETPOINTS ...
Page 225: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 97 ...
Page 226: ...4 98 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL SYSTEM CHAPTER 4 SETPOINTS ...
Page 227: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 99 ...
Page 396: ...4 268 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL MONITORING CHAPTER 4 SETPOINTS ...
Page 526: ...6 22 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 6 METERING ...