![GE 845 Instruction Manual Download Page 105](http://html.mh-extra.com/html/ge/845/845_instruction-manual_130353105.webp)
CHAPTER 3: INTERFACES
SOFTWARE INTERFACE
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
3–31
Printing Values from a
Connected Device
A complete list of actual values can also be printed from a connected device with the
following procedure:
1.
Establish communications with the desired device.
2.
From the main window, select the
Online > Print Device Information
menu item
3.
The Print/Export Options dialog box will appear. Select
Actual Values
in the upper
section and select either
Include All Features
(for a complete list) or
Include Only
Enabled Features
(for a list of only those features which are currently used) in the
filtering section and click
OK
.
Actual values lists can be printed in the same manner by right clicking on the desired
device (in the device list) and selecting the
Print Device Information
option.
Loading Setpoints
from a File
CAUTION:
An error message occurs when attempting to upload a setpoint file with a revision
number that does not match the relay firmware. If the firmware has been upgraded
since saving the setpoint file, see Upgrading Setpoints Files to a New Revision for
instructions on changing the revision number of a setpoint file.
The following procedure illustrates how to load setpoints from a file. Before loading a
setpoints file, it must first be added to the 845 environment as described in the section,
Adding Setpoints Files to the Environment
.
1.
Select the previously saved setpoints file from the File pane of the 845 software main
window.
2.
Select the
Offline > Edit Settings File Properties
menu item and verify that the
corresponding file is fully compatible with the hardware and firmware version of the
target relay. If the versions are not identical, see
Upgrading Setpoint Files to a New
Revision
for details on changing the setpoints file version.
3.
Right-click on the selected file and select the
Write Settings File to Device
item.
4.
Select the target relay from the list of devices shown and click
Send
. If there is an
incompatibility, an error of the following type occurs:
If there are no incompatibilities between the target device and the settings file, the data is
transferred to the relay. An indication of the percentage completed is shown in the bottom
of the main window.
Summary of Contents for 845
Page 10: ...VIII 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 219: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 91 ...
Page 221: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 93 ...
Page 222: ...4 94 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL SYSTEM CHAPTER 4 SETPOINTS ...
Page 223: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 95 ...
Page 224: ...4 96 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL SYSTEM CHAPTER 4 SETPOINTS ...
Page 225: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 97 ...
Page 226: ...4 98 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL SYSTEM CHAPTER 4 SETPOINTS ...
Page 227: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 99 ...
Page 396: ...4 268 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL MONITORING CHAPTER 4 SETPOINTS ...
Page 526: ...6 22 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 6 METERING ...