4–26
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
DEVICE
CHAPTER 4: SETPOINTS
FLEXLOGIC OPERANDS
The following operands are added for CyberSentry.
Communications
The 8 Series relays have a two-stage communications capability. The base CPU supports
Modbus protocol through the Ethernet, USB, serial and WiFi port. In addition, the base CPU
also supports IEC 103, DNP serial, DNP TCP/IP, and TFTP protocol. Once the
communications module option is added to the base, the base Ethernet port becomes
disabled but the two Ethernet ports on the communications module have enhanced
communications capabilities such as IEC61850, IEC62439 parallel redundancy protocol
(PRP) and IEEE 1588 Precision Time Protocol (PTP). The communications CPU also supports
Modbus TCP, IEC 104, DNP TCP, TFTP, SFTP, and SNTP protocol.
RS485
On the rear card 8 Series relays are equipped with one RS485 serial communication port
and one 10/100 Mbps Ethernet port. The RS485 port has settings for baud rate and parity.
It is important that these parameters agree with the settings used on the computer or
other equipment connected to this port. A maximum of 32 relays can be daisy-chained
and connected to a DCS, PLC or a PC using the RS485 port.
Path
:
Setpoints > Device > Communications > RS485
BAUD RATE
Range: 9600, 19200, 38400, 57600, 115200
Default: 115200
PARITY
Range: None, Odd, Even
Default: None
PORT PROTOCOL
Range: Modbus, DNP 3.0, IEC 60870-5-103
Default: Modbus
LOGOUT, ORIGIN, TIMESTAMP:
Warning (4)
An event to indicate when a certain role
logged out or timed out.
RADIUS_UNREACH, ORIGIN,
TIMESTAMP:
Critical (2)
RADIUS server is unreachable. Origin: RADIUS
server IP address and port number.
CLEAR_EVENT_RECORDS,
ORIGIN, TIMESTAMP:
Warning (4)
Clear event records command was issued.
CLEAR_TRANSIENT_RECORDS,
ORIGIN, TIMESTAMP:
Notice (5)
Clear transient records command was
issued.
CLEAR_FAULT_REPORTS,
ORIGIN, TIMESTAMP:
Notice (5)
Clear fault reports command was issued.
CyberSentry FlexLogic Operand
Description
AUTHENTICATION FAIL
Operand set for Failed Authentication self test and
alarm
UNAUTH SETTING CHANGE ATTEMPT
Operand set for unauthorized setting change action
RADIUS SRV UNAVAILABLE
Operand set for RADIUS servers unavailable self test
Event Record
Level
Description
Summary of Contents for 845
Page 10: ...VIII 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 219: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 91 ...
Page 221: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 93 ...
Page 222: ...4 94 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL SYSTEM CHAPTER 4 SETPOINTS ...
Page 223: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 95 ...
Page 224: ...4 96 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL SYSTEM CHAPTER 4 SETPOINTS ...
Page 225: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 97 ...
Page 226: ...4 98 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL SYSTEM CHAPTER 4 SETPOINTS ...
Page 227: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 99 ...
Page 396: ...4 268 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL MONITORING CHAPTER 4 SETPOINTS ...
Page 526: ...6 22 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 6 METERING ...