CHAPTER 4: SETPOINTS
DEVICE
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
4–25
RADIUS SETTINGS
The following are settings that need to be configured through EnerVista, in order to set up
communication with a Radius server on 845. For configuring the RADIUS server itself,
consult the RADIUS documentation. An example is provided, see
Communications Guide
.
Table 4-3: Radius Settings
SECURITY EVENTS
•
The event recorder records the events described in the table Security Events.
Table 4-4: Security Events
Setting
Name
Description
Min
Max
Default
Unit
s
Minimum
Permission
s
Primary
Radius IP
Address
IP address of primary
Radius server.
Default value
indicates no Primary
Radius server is
configured, and so
Radius is disabled.
0.0.0.0
223.255.255.2
54
0.0.0.0
-
Administrat
or
Primary
Authenticati
on Port
Radius
authentication port
1
65535
1812
-
Administrat
or
Vendor ID
An identifier that
specifies Radius
vendor specific
attributes used with
the protocol.
1
65535
Value that
represents
General Electric
(2910)
-
Administrat
or
Radius
Authenticati
on Method
Authentication
method used by
Radius server.
Currently fixed to
EAP-TTLS.
EAP-TTLS EAP-TTLS
EAP-TTLS
-
Administrat
or
Timeout
Timeout in seconds in
between re-
transmission
requests
0
9999
10
sec Administrat
or
Retries
Number of retries
before giving up
0
9999
3
-
Administrat
or
Radius
Authenticati
on (Shared)
Secret
Shared Secret used in
authentication. It is
only displayed as
asterisks. This setting
must meet the
CyberSentry
password
requirements.
See
password
section
for
requireme
nts
245
characters
N/A
-
Administrat
or
Confirm
Radius
Authenticati
on (Shared)
Secret
Confirmation of the
shared secret. Only
display as asterisks.
See
password
section
for
requireme
nts
245
characters
N/A
-
Administrat
or
Event Record
Level
Description
FAILED_AUTH, ORIGIN,
TIMESTAMP
Warning (4)
A failed authentication with time stamp in
UTC time when it occurred.
USER_LOCKOUT, ORIGIN,
TIMESTAMP:
Error (3)
The user lockout has occurred because of
too many failed authentication attempts.
SETTING_CHG, ORIGIN,
TIMESTAMP:
Notice (5)
An event to indicate setting change(s).
LOGIN, ORIGIN, TIMESTAMP:
Warning (4)
An event to indicate when a certain role
logged in.
Summary of Contents for 845
Page 10: ...VIII 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 219: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 91 ...
Page 221: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 93 ...
Page 222: ...4 94 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL SYSTEM CHAPTER 4 SETPOINTS ...
Page 223: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 95 ...
Page 224: ...4 96 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL SYSTEM CHAPTER 4 SETPOINTS ...
Page 225: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 97 ...
Page 226: ...4 98 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL SYSTEM CHAPTER 4 SETPOINTS ...
Page 227: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 99 ...
Page 396: ...4 268 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL MONITORING CHAPTER 4 SETPOINTS ...
Page 526: ...6 22 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 6 METERING ...