![GE 845 Instruction Manual Download Page 457](http://html.mh-extra.com/html/ge/845/845_instruction-manual_130353457.webp)
CHAPTER 4: SETPOINTS
CONTROL
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
4–329
DEAD BUS VOLTS MAX
Range: 0.00 to 1.50 x VT in steps of 0.01 x VT
Default: 0.20 x VT
The setpoint establishes a maximum voltage magnitude for the Bus Voltage. Below this
magnitude, the Bus Voltage input used for Synchrocheck is considered “Dead” or de-
energized.
DEAD LINE VOLTS MAX
Range: 0.00 to 1.50 x VT in steps of 0.01 x VT
Default: 0.20 x VT
This setpoint establishes a maximum voltage magnitude for the Line Voltage. Below this
magnitude, the Line Voltage input used for Synchrocheck is be considered “Dead” or de-
energized.
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
The Synchrocheck is blocked when the selected operand is asserted. Typically 52a (the
circuit breaker closed) contact is used to block Synchrocheck (Synchrocheck is needed
only when the circuit breaker is open). Synchrocheck can be also blocked when the relay
is tripping.
OUTPUT RELAY X
For details see
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Self-reset
Summary of Contents for 845
Page 10: ...VIII 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 219: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 91 ...
Page 221: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 93 ...
Page 222: ...4 94 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL SYSTEM CHAPTER 4 SETPOINTS ...
Page 223: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 95 ...
Page 224: ...4 96 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL SYSTEM CHAPTER 4 SETPOINTS ...
Page 225: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 97 ...
Page 226: ...4 98 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL SYSTEM CHAPTER 4 SETPOINTS ...
Page 227: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 99 ...
Page 396: ...4 268 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL MONITORING CHAPTER 4 SETPOINTS ...
Page 526: ...6 22 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 6 METERING ...