4–30
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
DEVICE
CHAPTER 4: SETPOINTS
USB
The USB parameters are as follows:
IP Address: 172.16.0.2
IP Mask: 255.255.255.0
IP Gateway: 172.16.0.1
FASTPATH:
Whenever the device is rebooted, the USB cable needs to be unplugged and plugged in
again for proper communication to be established over USB.
FASTPATH:
Connecting multiple 8 Series relays over USB to a single PC is not possible because in the
case of USB, the IP address of the device 172.16.0.2 is constant.
Ethernet Ports
The following communication offerings are available.
Base Offering
Modes: 10/100 Mbps
One Port: RJ45
Protocol: Modbus TCP
Communications Card Option “C” - 2x Copper (RJ45) Ports
Modes: 10/100 MB
Two Ports: RJ45 (with this option both enabled ports are on the communications card; the
Ethernet port located on the base CPU is disabled)
Protocols: Modbus TCP, DNP 3.0, IEC 60870-5-104, IEC 61850 GOOSE, IEEE 1588, SNTP, IEC
62439-3 clause 4 (PRP)
Communications Card Option “S” - 2x ST Fiber Ports
Modes: 100 MB
Two Ports: ST (with this option both enabled ports are on the communications card; the
Ethernet port located on the base CPU is disabled)
Protocols: Modbus TCP, DNP 3.0, IEC 60870-5-104, IEC 61850 GOOSE, IEEE 1588, SNTP, IEC
62439-3 clause 4 (PRP)
Wavelength: 1310 nm
Typical link distance: 4 km
Network Settings Menu
The following are the network settings menu of the 845 to accommodate the features of
the 845 product. If the communications card is installed network port 1 is no longer
available. When using more than one Ethernet port, configure each to belong to a different
network or subnet using the IP addresses and mask, else communication becomes
unpredictable when more than one port is configured to the same subnet.
NOTE
NOTE:
The softkeys and Down/Up key can be used to enter an IP address. When entering an IP
address you must press the “Back” key first to switch between softkey mode and the
Down/Up key mode.
NETWORK 1, 4, 5, PRT1(4,5) IP ADDRESS
Range: Standard IPV4 Address format
Default: 169.254.3.3 (Port 1)
Default: 127.0.0.1 (Port 4, 5)
The setting sets the port’s IPV4 address in standard IPV4 format.
NOTE
NOTE:
The setting is valid on port 1 if the optional communications card is not present.
The setting is valid on port 5 if port 4’s OPERATION is set to INDEPENDENT.
Summary of Contents for 845
Page 10: ...VIII 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 219: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 91 ...
Page 221: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 93 ...
Page 222: ...4 94 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL SYSTEM CHAPTER 4 SETPOINTS ...
Page 223: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 95 ...
Page 224: ...4 96 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL SYSTEM CHAPTER 4 SETPOINTS ...
Page 225: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 97 ...
Page 226: ...4 98 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL SYSTEM CHAPTER 4 SETPOINTS ...
Page 227: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 99 ...
Page 396: ...4 268 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL MONITORING CHAPTER 4 SETPOINTS ...
Page 526: ...6 22 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 6 METERING ...