CHAPTER 4: SETPOINTS
DEVICE
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
4–17
SNTP FUNCTION
Range: Disabled, Enabled
Default: Disabled
SNTP SERVER IP ADDRESS
Range: Standard IP Address Format
Default: 0.0.0.0
SNTP UDP PORT NUMBER
Range: 0 to 65535 in steps of 1
Default: 123
SNTP SERVER 2 IP ADDRESS
Range: Standard IP Address Format
Default: 0.0.0.0
SNTP 2 UDP PORT NUMBER
Range: 0 to 65535 in steps of 1
Default: 123
FASTPATH:
The SNTP and PTP settings take effect after rebooting the relay.
Security
The following security features are available:
•
Basic Security
– The basic security feature present in the default offering of the
product.
•
CyberSentry
– The feature refers to the advanced security options available as a
software option. When this option is purchased, it is automatically enabled and Basic
Security is disabled.
GENERAL RULES FOR ROLES
•
All the roles are password protected, except for the Observer role which is user
defined on the device. A user with Observer capability defined on the Radius is
password protected.
•
All the roles, except for the Observer role, support only one session at one time.
•
The Observer role has read-only access to all values in the relay except for one service
command which is described in the Password Recovery Procedure section.
•
All the roles, except for the Observer, have access to a “log out” setting, which has the
effect of switching to Observer role.
•
A Setpoint access setting for bypassing security is available. If this feature is used, the
user gains total access for any operations / configuration changes executed either
from the front panel or from EnerVista.
•
The setpoint access setting may be either switched directly on or assigned to a digital
input.
•
If the setpoint access setting is assigned to a digital input, the digital input needs to be
activated through a physical key (jumper).
•
The setpoint access setting may be set only by an Administrator.
PASSWORD COMPLEXITY
The password complexity is available on both Basic Security and CyberSentry.
If password complexity is enabled, a user account requires an alpha-numeric password
that meets the following requirements:
•
Passwords cannot contain the user account name or parts of the user's full name that
exceed two consecutive characters
Summary of Contents for 845
Page 10: ...VIII 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 219: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 91 ...
Page 221: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 93 ...
Page 222: ...4 94 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL SYSTEM CHAPTER 4 SETPOINTS ...
Page 223: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 95 ...
Page 224: ...4 96 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL SYSTEM CHAPTER 4 SETPOINTS ...
Page 225: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 97 ...
Page 226: ...4 98 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL SYSTEM CHAPTER 4 SETPOINTS ...
Page 227: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 99 ...
Page 396: ...4 268 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL MONITORING CHAPTER 4 SETPOINTS ...
Page 526: ...6 22 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 6 METERING ...