CHAPTER 7: MAINTENANCE
M3 BREAKER MAINTENANCE
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
7–7
Figure 7-7: Close Coil circuit with continuous monitoring
The following path is available using the keypad. For instructions on how to use the
keypad, please refer to
Chapter 3 - Working with the Keypad
.
PATH
:
MAINTENANCE > M3 BKR MAINTENANCE
CLOSE COIL FUNCTION
Range: Disabled, Alarm, Latched Alarm
Default: Disabled
For details see
The “ALARM” and “MAINTENANCE” LEDs will light up upon detection of a close coil
circuitry problem.
CLOSE COIL DELAY
Range: 1 to 10 sec in steps of 1 sec
Default: 5 s
This setting defines the Close Coil Monitor Delay, before targets appear on the display,
“ALARM” and “MAINTENANCE” LEDs light up on the front panel, and selected output
relays operate.
BYPASS BKR STATUS
Range: Disabled, Enabled
Default: Disabled
Set the “BYPASS BKR STATE” to Enabled when a by-pass resistor is connected across the
breaker auxiliary contact for continuous Close circuit integrity monitoring. The circuits
will be monitored regardless of breaker position. When “BYPASS BKR STATE” is set to
Disabled, monitoring of the close coil will be blocked when the breaker is closed.
OUTPUT RELAY X
Range: Do not operate, Operate
Default: Do not operate
For details see
Close
Coil
DC -
R By-pass
resistor
52b contact
External
jumper
V
B4
B5
DC +
Close - form A contacts
898793.cdr
A4