6–148
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
S4 CONTROLS
CHAPTER 6: SETPOINTS
–
Dead Line-Live Bus: the Closing permission signal is issued for a dead line and live
bus Condition (without voltage at the side of the breaker that correspond to the
line voltage).
–
Any Line-Dead Bus: the Closing permission signal is issued for any line but dead
bus Condition (without voltage at the side of the breaker that correspond to the
bus voltage).
–
Dead Line-Any Bus: the Closing permission signal is issued for any bus but a dead
line Condition (without voltage at the side of the breaker that correspond to the
line voltage).
–
One Live-Other Dead: the Closing permission signal is issued if bus and line
Condition are different.
–
Not Both Live: for if bus and line Condition are not both live.
BYPASS
Range: Off, On, Contact Input 1 to 10, Virtual Input 1 to 32, Remote Input 1 to 32, Logic
Element 1 to 16
Default: Off
This setting allows the user to bypass the Synchrocheck function by force by selecting
On, Contact Input, Virtual Input, or Remote Input.
BLOCK
For details see
OUTPUT RELAYS X
For details see