350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
M7 TESTING
CHAPTER 7: MAINTENANCE
M7 Testing
The Test Mode for 3 Series relays consists of testing front panel LEDs and Outputs Relays
The test mode state is indicated on the relay faceplate by a combination of the
Maintenance LED (faceplate option E), the In-Service LED, the Trouble LED, and the critical
fail relay, as shown in the following table.
The following cases should be considered when using Test Mode:
1.
When the relay is tripped, Test Mode cannot be Enabled.
Changing Force LEDs or Force Output Relays to "Enabled" will have no effect. The
value "Enabled" will not be accepted, and the value "Disabled" will be kept.
2.
If the relay is in Force LEDs test mode, and trips, the relay leaves Test Mode and the
Force LEDs setting automatically changes to "Disabled".
NOTE
NOTE:
Performing tests such as Forcing Output Relays should be carefully planned. Fault
conditions are not detected by the relay while in Force Output Relays mode, since the
protection and control elements are not operational during this mode.
Force LEDs
The LED lamp test is allows you to turn on each front panel LED individually. Testing the
LEDs is only available from the relay front panel.
The following path is available using the keypad. For instructions on how to use the
keypad, please refer to
Chapter 3 - Working with the Keypad
.
PATH
:
MAINTENANCE > M7 TESTING > FORCE LEDS
FORCE LEDS
Range: Disabled, Enabled
Default: Disabled
When the Force LEDs setpoint is set to Enabled, the relay Maintenance LED starts
flashing (faceplate option E), the In-service LED turns off, and the Critical Failure Relay is
de-energized, indicating the relay is in test mode.
LED 1(12)
Range: Off, On
Default: Off
Tests
Test Mode Faceplate
Option
Output Relay
setting
In-Service
LED
Trouble
LED
Maintenance
LED
Critical fail relay
(output 7)
Prot. & Control
elements
All Test =
Disabled
Disabled
E, L
Normal
operation
Not
affected
Not
affected
Not affected Normal
operation
Normal
operation
Force LED =
Enabled
Enabled
E
Normal
operation
Blinking
GREEN
Not
affected
Off
Energized
Normal
operation
Force Output =
Enabled
Enabled
E
Controlled from
Test settings
Off
Blinking
Orange
On
De-energized
Not operational
All Test =
Enabled
Enabled
E
Controlled from
Test settings
Off
Blinking
Orange
Off
De-energized
Not operational
Force LED =
Enabled
Enabled
L
Normal
operation
Blinking
GREEN
Not
affected
Off
Energized
Normal
operation
Force Output =
Enabled
Enabled
L
Controlled from
Test settings
Off
Blinking
Orange
Off
De-energized
Not operational
All Test =
Enabled
Enabled
L
Controlled from
Test settings
Off
Blinking
Orange
Off
De-energized
Not operational