such connections, the trickle current will be maintained by the resistor when the breaker is
open. For these applications the setting for “BYPASS BKR STATUS” should be set to
ENABLED.
Figure 7-4: Trip circuit with continuous monitoring
The following path is available using the keypad. For instructions on how to use the
keypad, please refer to
Chapter 3 - Working with the Keypad
.
PATH
:
MAINTENANCE > M3 BKR MAINTENANCE > TRIP COIL
TRIP COIL FUNCTION
Range: Disabled, Alarm, Latched Alarm
Default: Disabled
For details see
The “ALARM” and “MAINTENANCE” LEDs will light up upon detection of a trip coil circuitry
problem.
TRIP COIL DELAY
Range: 1 to 10 sec in steps of 1 sec
Default: 5 s
This setting defines the Trip Coil Monitor Delay, before targets appear on the display,
“ALARM” and “MAINTENANCE” LEDs light up on the front panel, and selected output
relays operate.
BYPASS BKR STATUS
Range: Disabled, Enabled
Default: Disabled
Set the “BYPASS BKR STATE” to Enabled when a by-pass resistor is connected across the
breaker auxiliary contact for continuous Trip circuit integrity monitoring. The circuits will
be monitored regardless of breaker position. When “BYPASS BKR STATE” is set to
Disabled, monitoring of the trip coil will be blocked when the breaker is open.
OUTPUT RELAY X
Range: Do not operate, Operate
Default: Do not operate
For details see
Trip
Coil
DC -
R By-pass
resistor
52a contact
External
jumper
V
A2
B3
A3
DC +
Trip - form A contacts
898787.cdr