3–10
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
FRONT CONTROL PANEL INTERFACE
CHAPTER 3: INTERFACES
* Failure is logged after the detection of 5 consecutive failures - that is after 25 seconds
Table 3-2: Major Self-test Errors
* Failure is logged after the detection of 5 consecutive failures - that is after 25 seconds
Flash messages
Flash messages are warning, error, or general information messages displayed in response
to pressing certain keys. The factory default flash message time is 4 seconds.
Figure 3-7: Typical Flash message
SETPOINT STORED
This flash message is displayed in response to the
ENTER
key while on any setpoint
message (see example above). The edited value was stored as entered.
COMMAND EXECUTED
This flash message is displayed in response to executing a command: ON, OFF, YES, NO,
etc.
INVALID PASSWORD
This flash message appears upon an attempt to enter an incorrect password, as part of
password security.
AR IN PROGRESS
This flash message appears when the Autoreclosure is in progress performing the
configured sequence.
MAINTENANCE
ALERT: High
Ambient
Temperature
No
The ambient
temperature is
above 80
o
C.
Every 1 hour
Increase ventilation to the
surroundings.
MAINTENANCE
ALERT:
Daughter Error
No
The rear
Communications
daughter board type
does not match the
order code.
Every 5 seconds*
Replace the rear
communications
daughter board with the
correct board.
MAINTENANCE
ALERT: Comms
Serial Invalid
No
The internal
communications
board does not
match the order
code.
Every 5 seconds*
Contact factory.
Self-test Error
Message
Latched
Target
Message?
Description of
Problem
How Often the Test
is Performed
What to do
UNIT FAILURE:
Contact
Factory (XXXX)
Yes
This warning is
caused by a unit
hardware failure.
Failure code (XXXX) is
shown.
Every 5 seconds*
Contact the factory and
provide the failure code.
RELAY NOT
READY: Check
Settings
No
PRODUCT SETUP
INSTALLATION
setting indicates that
relay is not in a
programmed state.
On power up and
whenever the
PRODUCT SETUP
INSTALLATION
setting is altered.
Program all required
settings then set the
PRODUCT SETUP
INSTALLATION setting to
"Programmed".
Self-test Error
Message
Latched
Target
Message?
Description of
Problem
How Often the Test
is Performed
What to do