CHAPTER 6: SETPOINTS
S3 PROTECTION
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
6–41
PH TOC DIRECTION
Range: Disabled, Forward, Reverse
Default: Disabled
This setting provides control to the Phase TOC function in terms of permitting operation
upon fault conditions in the selected current flow direction, and blocking it when faults
occur in the opposite direction.
A special case is considered when fault direction is undefined. Then “BLK OC DIR UN”
setting in Neutral Directional defines the fault direction.
OUTPUT RELAY X
For details see
BLOCK 1/2/3
For details see