350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
QUICK SETUP SETTINGS
CHAPTER 5: QUICK SETUP - FRONT CONTROL PANEL
PH IOC1 FUNCTION
Range: Disabled, Trip, Latched Alarm, Alarm
Default: Disabled
↘
PH IOC1 PICKUP
Range: 0.05 to 20.00 x CT
Default: 1.00 x CT
GND IOC1 FUNCTION
Range: Disabled, Trip, Latched Alarm, Alarm
Default: Disabled
↘
GND IOC1 PICKUP
Range: 0.05 to 20.00 x CT
Default: 1.00 x CT
SENS GND IOC1 FUNCTION [WHEN SPECIFICALLY ORDERED]
Range: Disabled, Trip, Latched Alarm, Alarm
Default: Disabled
↘
SENS GND IOC1 PICKUP
Range: 0.005 to 3.000 x CT
Default: 1.000 x CT
NTRL IOC1 FUNCTION
Range: Disabled, Trip, Latched Alarm, Alarm
Default: Disabled
↘
NTRL IOC1 PICKUP
Range: 0.05 to 20.00 x CT
Default: 1.00 x CT
NOTE
NOTE:
The settings changed using the Quick Setup menu, are available for review and
modification by navigating through
S1 RELAY SETUP
,
S2 SYSTEM SETUP
and
S3
PROTECTION
in the
SETPOINTS
main menu.