INSTALLATION Continued

and strain relief, and connected to the appropriate power 

supply by a certified electrician in accordance with local 

codes.

Gas Connection

ENSURE THE GAS METER AND GAS PIPING ARE SIZED 

CORRECTLY FOR THE AMOUNT OF GAS FLOW AND PRESSURE 

THAT WILL BE NEEDED TO RUN ALL APPLIANCES IN THE 

KITCHEN.  UNDERSIZED GAS PIPING INTO THE KITCHEN 

MAY AFFECT THE PERFORMANCE OF THIS AND/OR OTHER 

EQUIPMENT.  IF IN DOUBT, CONSULT YOUR LOCAL GAS 

AUTHORITY.

A MANUAL OR AUTOMATIC ISOLATION VALVE MUST BE 

INSTALLED ON THE GAS SUPPLY TO THE KITCHEN FOR 

ACCESS IN THE EVENT OF AN EMERGENCY.  THE MANUAL 

VALVE OR AUTOMATIC VALVE ACCESS POINT SHOULD BE 

READILY ACCESSIBLE AND LOCATED EITHER OUTSIDE THE 

KITCHEN OR CLOSE TO AN EXIT.  POST THE FOLLOWING 

NOTICE AT THE MANUAL VALVE OR AUTOMATIC VALVE 

ACCESS POINT:

“ALL DOWNSTREAM BURNER AND PILOT VALVES MUST 

BE TURNED OFF PRIOR TO RESTORING THE GAS SUPPLY.  

AFTER AN EXTENDED SHUT OFF, PURGE BEFORE 

RESTORING GAS.”

1.  A manual gas shut-off valve must be installed in the gas 

supply line ahead of the appliance for safety and ease 

of future service.  The shut-off valve should be located 

such that it can be reached quickly in the event of an 

emergency.  The shut-off valve is normally supplied by the 

installer.

2.  This unit is shipped with a gas pressure regulator.  It must 

be installed at the appliance prior to connecting the 

equipment to the gas line. Each appliance must have its 

own pressure regulator.  Be sure to install the regulator 

according to the gas flow direction and verify that the 

pressure marking corresponds with the gas type.  Failure 

to install a regulator will void the equipment warranty.

PRIOR TO CONNECTING THE REGULATOR, CHECK THE GAS 

SUPPLY LINE PRESSURE.  THE REGULATOR SUPPLIED WITH 

THE UNIT IS RATED FOR A MAXIMUM OF ½ PSI (14” WC).  IF 

THE GAS SUPPLY LINE PRESSURE EXCEEDS THIS MAXIMUM, 

A STEP DOWN REGULATOR WILL BE REQUIRED AND MUST BE 

INSTALLED IN ACCORDANCE WITH LOCAL CODES.

THE RED AIR-VENT CAP IS PART OF THE REGULATOR AND 

SHOULD NOT BE REMOVED, UNLESS LOCAL CODES REQUIRE 

EXTERNAL VENTING.  IF EXTERNAL VENTING IS REQUIRED, 

INSTALL IN ACCORDANCE WITH LOCAL CODES.

3.  A certified flexible gas hose and quick disconnect 

assembly with suitable strain relief is recommended for 

connection from the gas supply line to the unit.  This will 

allow the unit to be moved for future service.

FLEXIBLE HOSES & QUICK DISCONNECT DEVICES MUST 

COMPLY WITH ALL LOCAL AUTHORITIES AND CODES.  

IN NORTH AMERICA THIS INCLUDES ANSI Z21.69/CSA 

6.16, ADDENDA Z21.69B-2006/CSA 6.16B-2006 (OR 

LATEST EDITION) AND ANSI Z21.41/CSA 6.9, ADDENDA 

Z21.41A-2005/CSA 6.16A-2005 (OR LATEST EDITION).

4.  Only connect this unit to the type of gas shown on the 

rating plate.  Operating this unit with the wrong gas type 

can result in abnormal performance, property damage, 

injury or death.

5.  Ensure that any new piping, joints and connections have 

been made in a clean manner, so that dirt, threading 

chips and/or other foreign matter will not clog pilots, 

valves and/or controls.  If necessary, purge new piping 

prior to connecting the appliance.  Use pipe sealant that 

is certified for use with liquefied petroleum, for new joints 

and/or connections, where sealant is required.

6.  When pressure testing the gas supply piping to a 

maximum of ½ psi (14” WC, 3.45 KPa), the appliance must 

be isolated from the supply line by closing the manual 

shut-off valve.

7.  To ensure optimal operation of this unit, it is 

recommended that the dynamic gas supply pressure into 

the appliance regulator is a minimum of 1” WC higher than 

the pressure stated on the rating plate.

Start Up

1.  Inside the unit, ensure the burners are in the correct 

position and the shields hanging under the burners have 

not rotated out of position during transit.

2.  Install cast radiants over each burner and place the 

cooking grates in position on the unit.

3.  Ensure the gas supply to the appliance is open and the 

unit is connected to the power supply.  Activating the one 

or two power switches on the right leg operates the unit.

4.  Check all gas connections for leaks using a soap solution.  

Do not use an open flame to check for leaks.  Be sure to 

inspect connections outside and inside the unit (ie: valves, 

manifold fittings and connections in the left leg channel) 

to make certain all connections are gas tight after 

shipping.

5.  Verify the unit is running at the pressure stated on the 

rating plate as follows:

Summary of Contents for HEEGM XX CL

Page 1: ...0 USA Sales Parts and Service 1 800 424 2411 Canadian Sales 1 888 442 7526 Canada or USA Parts Service 1 800 427 6668 Part 4530868 04 25 12 2012 Garland Commercial Ranges Ltd FOR YOUR SAFETY DO NOT ST...

Page 2: ...uld expose you to airborne particles of glass wool ceramic fibers Inhalation of airborne particles of glass wool ceramic fibers is known to the state of California to cause cancer Operation of this pr...

Page 3: ...STALLATION 6 General 6 Positioning and Setup 6 Optional Stand 7 Air Supply and Ventilation 7 Electrical Connection 7 Gas Connection 8 Start Up 8 USE AND CARE 9 Operation 9 Warnings 11 Optional Equipme...

Page 4: ...EGM36CL 45 1143 45 1143 25 1 2 648 6 87 000 78 000 420 191 29 9 0 846 HEEGM48CL 65 1651 45 1143 25 1 2 648 9 130 500 117 000 254 560 43 2 1 223 HEEGM60CL 65 1651 45 1143 25 1 2 648 11 159 500 143 000...

Page 5: ...vidually controlled by a manual high low valve 9 ft power cord with NEMA 5 15P plug for standard 120V models Wire brush and scraper combination tool included for cleaning grates gas regulator for appl...

Page 6: ...e rating plate contains other important information critical to the proper installation of the unit It specifies the gas type gas pressure voltage and clearance requirements for the appliance INSTALLA...

Page 7: ...T USE AN EXTENSION CORD TO CONNECT THIS UNIT TO A POWER SUPPLY DO NOT USE THIS APPLIANCE IF THE POWER CORD IS DAMAGED DO NOT ATTEMPT TO REPAIR A DAMAGED POWER CORD TAKE CARE NOT TO EXPOSE THE POWER CO...

Page 8: ...ING IS REQUIRED INSTALL IN ACCORDANCE WITH LOCAL CODES 3 A certified flexible gas hose and quick disconnect assembly with suitable strain relief is recommended for connection from the gas supply line...

Page 9: ...TURN THE POWER OFF AND CLOSE THE MANUAL SHUT OFF VALVE TO THE APPLIANCE CONTACT AN AUTHORIZED SERVICE AGENT FOR SERVICE BEFORE ATTEMPTING TO RESTORE GAS SUPPLY FOR A LIST OF AUTHORIZED SERVICE AGENTS...

Page 10: ...TCH BURNERS ON OFF LEFT SIDE BURNERS ON OFF RIGHT SIDE BURNERS ON OFF MAIN POWER ON OFF BURNERS ON OFF MAIN POWER ON OFF RIGHT SIDE BURNERS ON OFF LEFT SIDE BURNERS ON OFF USE AND CARE Continued 7 To...

Page 11: ...grease tray are possible with this type of appliance and excessive amounts of grease in the tray can lead to a sustained flare up or fire which can be dangerous and result in personal and or property...

Page 12: ...s to stick even more When cleaning cast iron components such as the cooking grates radiants and burners do not handle these components roughly Dropping them on the floor or in the sink may cause them...

Page 13: ...ess steel Never spray or pour water on the unit to clean Always disconnect electrical power before cleaning accessible panels Weekly Periodic Cleaning In addition to the daily cleaning tasks outlined...

Page 14: ...e agency All repairs must be performed by a qualified technician using genuine Garland replacement parts or risk negating the warranty For a list of Authorized Service Agents to view a Genuine Parts l...

Page 15: ...Part 4530868 04 25 12 Page 15...

Page 16: ......

Page 17: ...Pi ce n 4530868 04 25 12 Page 16...

Page 18: ...Pi ce n 4530868 04 25 12 Page 15...

Page 19: ...es performances et pour effectuer les r glages n cessaires De plus un nettoyage derri re les panneaux non accessibles comme le panneau avant et ou les panneaux des pieds doit galement tre effectu lors...

Page 20: ...nneuse chaude 3 3 Gratter la goutti re graisse et la rigole en dirigeant la graisse et les d bris dans le s tiroir s graisse Vider le s tiroir s graisse en grattant la graisse les d bris attach s Lave...

Page 21: ...ge des composants en fonte comme les grilles de cuisson les radiants et les br leurs ne pas manipuler ces composants avec brutalit Le fait de les laisser tomber sur le sol ou dans l vier peut causer d...

Page 22: ...tre maintenu contre le plateau de fa on ne pas obstruer la circulation de l air vers et autour de l unit en particulier entre le plateau graisse et le panneau des robinets Il est important que les pl...

Page 23: ...d Ed Ed ZZhWd WZ E W D Z ZZ d Zk hZ h hD d Ed Zk hZ hD d Ed Zk hZ hD d Ed Zk hZ ZK d hD d Ed Zk hZ ZK d hD d Ed Ed ZZhWd WZ E W D Z ZZ d UTILISATION ET ENTRETIEN suite 7 Pour arr ter l unit il suffit...

Page 24: ...ourner l obturateur pour laisser PLUS d air entrer dans la cavit du br leur Si les flammes semblent se d tacher des orifices du br leur tourner l obturateur pour laisser MOINS d air entrer dans la cav...

Page 25: ...ON DE LA CONDUITE D ALIMENTATION D PASSE CETTE VALEUR MAXIMALE UN R GULATEUR R DUCTEUR SERA N CESSAIRE ET DEVRA TRE INSTALL CONFORM MENT AUX CODES LOCAUX LE BOUCHON DE VENTILATION FAIT PARTIE DU R GUL...

Page 26: ...fi en cas de doute sur la prise de courant NE PAS UTILISER DE RALLONGE POUR CONNECTER CETTE UNIT UNE PRISE DE COURANT NE PAS UTILISER CET APPAREIL SI LE CORDON D ALIMENTATION EST ENDOMMAG NE PAS ESSAY...

Page 27: ...cis La plaque signal tique contient d autres informations importantes essentielles pour l installation correcte de l unit Elle sp cifie le type et la pression du gaz la tension et les exigences de d g...

Page 28: ...net de r glage manuel Cordon d alimentation de 9 pieds avec prise NEMA 5 15P pour les mod les 120 V standard Outil avec brosse m tallique et grattoir combin s inclus pour le nettoyage des grilles R gu...

Page 29: ...52 000 280 127 29 9 0 846 HEEGM36CL 45 1143 45 1143 25 1 2 648 6 87 000 78 000 420 191 29 9 0 846 HEEGM48CL 65 1651 45 1143 25 1 2 648 9 130 500 117 000 560 254 43 2 1 223 HEEGM60CL 65 1651 45 1143 2...

Page 30: ...nement et installation 6 Socle en option 7 Alimentation en air et ventilation 7 Raccordement lectrique 7 Connexion du gaz 8 D marrage 8 UTILISATION ET ENTRETIEN 9 Fonctionnement 9 Avertissements 11 qu...

Page 31: ...res de laine de verre fibres c ramiques L inhalation de ces particules de laine de verre ou de fibres c ramiques est reconnue par l tat de Californie comme causant le cancer L utilisation de ce produ...

Page 32: ...ces et service U 1 800 424 2411 Ventes Canada 1 888 442 7526 Pi ces Service Canada ou U 1 800 427 6668 Pi ce n 4530868 04 25 12 2012 Garland Commercial Ranges Ltd POUR VOTRE S CURIT NE PAS STOCKER NI...

Reviews: