10 Base Load Sequencing (BLS)
TM
72 / 80
USA
January 2015
"Remote On-Load" digital output
Do not use this output to switch the compressor on
and off.
This output switches the compressor to On-Load.
This remote On-Load signal should be active
when the programmable output "
Enable Remote
On-Load
" is sent to the compressor controller.
"Remote Partial On-Load" digital output
This output is not used for this application.
Connection assignments and examples
Connection assignment
Connec-
tion
Function
6
COM
7
110...230 V UC
8
"Operating" digital
input
24...48 V UC
9
COM
10
110...230 V UC
11
"Motor" digital input
24...48 V UC
12
COM
13
110...230 V UC
14
"On-Load" digital
input
24...48 V UC
16
(~) (+)
17
Power supply
110...230 V AC/DC
(±)10%
(~) (-)
21
COM
22
NC
23
"Enable Remote
On-Load" digital
output
NO
26
COM
27
NC
28
"Remote On-Load"
digital output
NO
31
COM
32
NC
33
"Remote Partial On-
Load" digital output
NO
Chart 10-12: Connection assignment
Compressor status messages
Compressor module (STD)
Operating
Load
Motor
Power supply
Mains contactor
Control valve
"Operating" or
Collective error signal
Supply voltage
6+7:110..230 V UC
6+8:24..48 V UC
12+13:110..230 V UC
12+14:24..48 V UC
9+10:110..230 V UC
9+11:24..48 V UC
16+17:
110..230 V UC
Fig. 10-18: Connections for status messages
Controlling a compressor with a line pressure
sensor and electronic compressor control
(example)
Enable
Remote
On-Load
Remote
Partial
On-Load
Remote
On-Load
21 23
26 28
31 33
Compressor module (STD)
Digital Input
Enable
Remote On-Load
Digital Input
Remote On-Load
Electronic compressor controller
Fig. 10-19: Line pressure sensor and electronic com-
pressor controller
Controlling a compressor with a line pressure
switch (example)
NOTICE
Property damage
If a compressor module (STD) is installed, the
pressure switch on the compressor may no
longer provide any protective against overpres-
sure.
➯
For compressors that are not equipped with
an independent overpressure detection
system, it is recommended that a pressure
switch be integrated in the fault circuit of the
compressor, so that any local overpressure
situation will stop the compressor indepen-
dently of the GD PILOT TS master.