7
Clearing a fault
TM
50 / 80
USA
January 2015
Display
Potential root cause
Remedy
A608
Dryer
(compressor without speed con-
trol)
Fault of integrated or external
dryer.
3)
See the chapter on the integrated
dryer in the compressor operating
instructions.
A608
Dryer
(compressor with speed control)
Fault from external dryer.
3)
Check and look for root cause.
A609:
Condensate Drain
Connected condensate drainage
valves (Bekomat) defective
3)
Check and look for root cause.
A610:
Fine precipitator
Fine precipitator differential pres-
sure is too high
3)
Check and replace fine separator
if necessary.
A611:
Air Filter
Air filter differential pressure is
too high
3)
Check and replace air filter if nec-
essary.
A612:
Oil Filter
Oil filter differential pressure is
too high
3)
Check and replace oil filter if nec-
essary.
A613:
Oil level low
Oil level too low.
3)
Check and top up oil if neces-
sary.
A614:
Oil temperature high
High oil temperature.
3)
Check and look for root cause.
A615:
External Warning
Warning from an external
device.
3)
Check and look for root cause.
A616:
Lubrication System
A fault has occurred in the motor
lubrication system, or the LC unit
is empty.
3)
See the chapter on the motor
lubrication system in the com-
pressor system operating instruc-
tions.
A617:
Setting Input 1
The programmable digital input
1 has been actuated, but is pro-
grammed as [Open].
3)
Check the corresponding input
assignment.
3)
A618:
Setting Input 2
The programmable digital input
2 has been actuated, but is pro-
grammed as [Open].
3)
Check the corresponding input
assignment.
3)
A619:
Setting Input 3
The programmable digital input
3 has been actuated, but is pro-
grammed as [Open].
3)
Check the corresponding input
assignment.
3)
A620:
Setting Input 4
The programmable digital input
4 has been actuated, but is pro-
grammed as [Open].
3)
Check the corresponding input
assignment.
3)
A621:
Setting Input 5
The programmable digital input
5 has been actuated, but is pro-
grammed as [Open].
3)
Check the corresponding input
assignment.
3)
A622:
Setting Input 6
The programmable digital input
6 has been actuated, but is pro-
grammed as [Open].
3)
Check the corresponding input
assignment.
3)
Chart 7-5: Warnings triggered by the compressor (A600 - A695)