4
Menus
TM
20 / 80
USA
January 2015
SD-Card
SD-Card
Record Data
State of SD-Card
OK
Off
File Name
Ready
Before Removing SD-Card
switch Record Data to Off.
Fig. 4-19: "
SD-Card
" submenu
The controller has a data recording function (data
logger) on an SD-Card.
The data recording function can be switched on
and off in this menu. See chapter "Additional Op-
eration / Data Recording".
4.6
"
Fault History
" menu
The controller saves the last 64 alarms (Faults and
Warnings) that have occurred.
The alarms are displayed in a list, with the most
recent alarm at the top of the list. If the list ex-
ceeds 64 alarms, the oldest alarm at the end of
the list will be overwritten.
A flashing symbol to the left of the alarm indi-
cates that this alarm is active (has not yet been re-
set). The symbol also flashes on the register card
<
Fault History
>.
Fault Overview
Fault History
Reset
Warning A622
Input 6
Fault E400
Power Supply Failure
Fault E402
Motor Temperature
Warning A621
Input 5
Warning A620
Input 4
Warning A619
Input 3
Warning A618
Input 2
Warning A617
Input 1
Fig. 4-20: "
Fault History
" menu
Each alarm is save with the date and time when it
occurred.
The arrow keys can be used to scroll through the
alarm list.
The <
i
> button at the right side of the menu line
displays the measured values captured at the
time of the alarm, in addition to further information
about each alarm.
Fault History
Fault E400:
Power Supply Failure
When 29.Jan.2013, 15:53:23
Hours Run 2h
TotalCount 5
Status Ready to start
Discharge pressure 6.3bar
Output temperature 30°C
Line pressure 7.5 bar
Speed 0rpm
Heatsink temp. 31°C
Motor current 0.0AMP
Fig. 4-21: Information about the selected alarm
The arrow keys can be used to scroll through the
contents.
Acknowledge alarm
After the cause of the alarm has been corrected,
the alarm must be reset in the controller.
1
Correct the cause of the alarm.
2
Press the register card <
Fault History
>.
3
Press the <
Reset
> button.
✓
The alarm, or all current alarms, are reset.
– The flashing alarm symbol disappears.
– The symbol stops flashing on the register
card <
Fault History
>.
Alarms that are still present cannot be reset. The
alarm symbol and the symbol on the register card
<
Fault History
> continue to flash.
4.7
"
Access Code
" menu
Codes for special operating options can be en-
tered in the "
Access Code
" menu.
The following access codes are available to the
customer's personnel.
Code Operating function
1234 Activate and deactivate Base Load
Sequencing (option).
3022 Enable and disable user inputs; if dis-
abled, no parameters can be entered.
3091 Enable and disable maintenance level;
additional operating functions.
Chart 4-3: Customer access codes