Figure 11. Digital input setup screen
9.9.
Digital output setup
Total of four digital outputs on connector J104:
Digital output 1 (J104, pin 15)
Digital output 2 (J104, pin 17)
Digital output 3 (J104, pin 19)
Digital output 4 (J104, pin 37)
By default, all digital outputs are turned off (function set to off).
Digital output signal 0 - 5 V.
Available functions:
▪
OFF
▪
Pressure setpoint
▪
HV error
▪
HV output state
Pressure setpoint function:
ON pressure - When pressure value gets below this point, digital output is
asserted.
OFF pressure - When pressure value gets above this point, digital output is
de-asserted.
HV error function:
Digital output is asserted when supply error is detected.
HV output state function:
Digital output is asserted when supply is on (HV on), or de-asserted when
supply is off (HV off).
Supply source - Selects supply driving digital output.
Page 24
900034_C
900034_C - Touchscreen user interface