Set Points
With this feature, you can establish set point parameters: the set point number, what supply it
should monitor (whether it should monitor a bakeout), and the on/off pressure values. With each
set point parameter, if the set point has been used before, the present values are displayed.
Procedure
1.
Press
Set Points
(the
3
key). The bottom display shows 1 – 8 followed by a flashing
sign to indicate that you may use the numerical keys to enter the desired set point.
2.
Key in the set point number and press
ENTER
.
1
2
3
4
5
6
7
8
Set Point
Set Point
Supply 1
Supply 2
Display
Select
Display
Select
Flashing
Sign
Options:
1 through 8
3.
The next parameter is SPT SUPPLY. An arrow points to the bottom
Display Select
key to show it is active. Press it to cycle through the options — DISABLED,
SUPPLY 1, SUPPLY 2, BAKE S1, and BAKE S2.
1
2
3
4
5
6
7
8
Set Point
Set Point
Supply 1
Supply 2
4.
When you reach the desired option, press
ENTER
.
5.
The next parameter is SETPT ON. The bottom display shows the current ON
pressure with the number flashing to indicate that you can use the numerical keys to
enter a new value (e.g. 2.0E-5 Torr).
1
2
3
4
5
6
7
8
Set Point
Set Point
Supply 1
Supply 2
6.
Key in the desired ON pressure value and press
ENTER
.
NOTE: If you change the ON pressure, OFF pressure default is reset to: ON pressure * 1.2
(20% hysteresis)
7.
The next parameter is SETPT OFF. Key in the desired OFF pressure value and press
ENTER
. Or press ENTER for 20% hysteresis.
1
2
3
4
5
6
7
8
Set Point
Set Point
Supply 1
Supply 2
8.
When the display asks you to CONFIRM, press
ENTER
to save your set point
parameters or
ESC
to exit without saving changes.
After you have finished
Digitel MPC Manual