IF 632 Installation and Operation Manual
Release: 3 01/31/01
59
Relay Module
RM-4
(30873)
Terminal
Number
Designator
Description
1
1 NO
Form C normally open contact
2
1 NC
Form C normally closed contact
3
1 C
Form C common contact 10A @ 30VDC or 220VAC resistive, fused @ 10A.
4
1 M
CCT #1 Relay feedback point to monitor status of controlled device
5
2 NO
Form C normally open contact
6
2 NC
Form C normally closed contact
7
2 C
Form C common contact 10A @ 30VDC or 220VAC resistive, fused @ 10A.
8
2 M
CCT #2 Relay feedback point to monitor status of controlled device
9
3 NO
Form C normally open contact
10
3 NC
Form C normally closed contact
11
3 C
Form C common contact 10A @ 30VDC or 220VAC resistive, fused @ 10A.
12
3 M
CCT #3 Relay feedback point to monitor status of controlled device
13
4 NO
Form C normally open contact
14
4 NC
Form C normally closed contact
15
4 C
Form C common contact 10A @ 30VDC or 220VAC resistive, fused @ 10A.
16
4 M
CCT #4 Relay feedback point to monitor status of controlled device
Relay Expansion Module
RM-4E
(30874)
Terminal
#
Designator
Description
1
5 NO
Form C normally open contact
2
5 NC
Form C normally closed contact
3
5 C
Form C common contact 10A @ 30VDC or 220VAC resistive, fused @ 10A
4
5 M
CCT #5 Relay feedback point to monitor status of controlled device
5
6 NO
Form C normally open contact
6
6 NC
Form C normally closed contact
7
6 C
Form C common contact 10A @ 30VDC or 220VAC resistive, fused @ 10A.
8
6 M
CCT #6 Relay feedback point to monitor status of controlled device
9
7 NO
Form C normally open contact
10
7 NC
Form C normally closed contact
11
7 C
Form C common contact 10A @ 30VDC or 220VAC resistive, fused @ 10A.
12
7 M
CCT #7 Relay feedback point to monitor status of controlled device
13
8 NO
Form C normally open contact
14
8 NC
Form C normally closed contact
15
8 C
Form C common contact 10A @ 30VDC or 220VAC resistive, fused @ 10A.
16
8 M
CCT #8 Relay feedback point to monitor status of controlled device
Building Control
Module
The building control module (BC) consists of three (3) assemblies. The
I/O Building
Control Module
, the
Building Control Expander,
and the
Building Control
Display/Switch Module.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com