IF 632 Installation and Operation Manual
Release: 3 01/31/01
154
Configuration Data Descriptions
File Variable
R:7 C:Smart Start Config
R:
Revision number of configuration file
C:
User configuration name or description (“Smart Start Config” is default) 20 char. Max.
System Variables
P:
xxxxxx
P
= Alarm prefix - up to 6 characters (“Fire” is default)
A:1 T:0 N:
A
= Node number (network firmware Only)
T
= Node type (network firmware Only)
0 = Individual type network (default @ SmartStart)
1 = Monolith type network (Not currently available)
N
= Node name - up to 20 characters (network firmware Only)
I:256 O:256
I
:Total number of input groups
O
:Total number of output groups
S:0
S
: System type
0=F 650
1=F 630
2=F 632
3=F 610
4=not used
B:00 L:18 A:0 S:0 P:1 C:3 M:0 I:16
B:
Total number of bypassed inputs & outputs in system
L:
Address of last valid card in system
A:
Remote Annunciator exists (1) or not (0)
S:
Silence Inhibit delay (0=0 see, 1=30sec, 2=1 min. 3=1min 30 see, 4=2min,
5=2min-30sec, 6=3 min. 7=3min-30sec, 8=4min, 9=4min-30sec, 10=5min)
P:
Coded Signal pulse period (0= 5sec, 1=1sec, 2=1.5sec, 3=2sec)
C:
Number of Coded Signal Cycles (0=1, 1=2, 2=3, 3=4, 4=5, 5=6, 6=7,7=8)
M:
Signal type after coded signals have been completed (0=Silence, 1 =March Time)
I:
Auto Silence time (0=2min, 1=2min 30sec, 2=3min, up to 26=15min {default = 10min}.