IF 632 Installation and Operation Manual
Release: 3 01/31/01
31
6.
The acknowledge switch red LED will begin to flash. This guided prompt
feature notifies the user that the next expected action is to press the "ACK"
switch - acknowledging the
Alarm Condition
. The panel will remain in an
alarm condition until all initiating devices are cleared and reset. At that time
the panel will return to normal quiescent condition. Should the city tie be
programmed for local energy master box trip, the city tie will be in trouble and
the box should be reset at this time.
•
NOTE
:
Table P4 - Word Dictionary defines the Word Types (1 -
5) used to describe the alarm location, device etc. See Table P4
found in Section 5 Programming for complete listing.
Status : ALARM 1st of 1 MM/DD/YY HH:MM
Fire Alarm in Ckt:#_ Dev:#_
Figure O-2
Display for Multiple Alarm(s)
•
NOTE
:
Multiple alarms are shown after the words ALARM
Total “x”; with “x” representing the total amount of alarms. See
Figure O-3.
Status : ALARM Total X MM/DD/YY HH:MM
Fire Alarm in Ckt:#_ Dev:#_
Figure O-3
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com