Main Power Supply
The main power supply (p/n 30889) is a combination 8 amp system power supply
and battery charger. It provides the system with five supplies (a 24Vdc
regulated, 24Vdc unregulated, 12Vdc, 5Vdc and the battery charger). The
standard battery charger is sized to maintain 5 to 60 AH batteries. The battery
charger card has three resistors for programming various battery sizes. R21 &
R17 should be removed when 5 - 20AH batteries are installed. R1 should be
removed when 21 - 40AH batteries are installed. No resistors should be removed
when 41 - 60AH batteries are used.
Installation
Diagram
Refer to drawings C-W856 Main Power Supply B-W471 Wiring, Minimum
System Flex 632 and B-W474 Wiring Basic Chassis for installation and cable
connections. When applicable, refer to C-W857 Aux. Power Supply.
Specifications
Input Voltage
120 VAC 50/60 Hz 3 amps Max. (Optional 220V AC
available)
Output Voltage
24 Volt DC regulated @ 4 Amps - system power, S+ S-
and A+ A-
{
XE "\"Smart Start\""
}
24 Volt DC filtered @ 4 Amps - for signal circuit power
5 Volt DC regulated - supply for logic circuits
12 Volt DC regulated @ 2 Amps
Operating Temperature 0 to +49 degrees C
Humidity
85% non-condensing
Interconnects
24 VAC
(2) secondary transformer connection
C+, C-
Connection (Red, Black) to Filter Capacitor
BO
(Brown-out Output)
Brown Out - connects to auxiliary power supply BI
(Brown-out Input) terminal
B+, B-
(Red, Black) connections to Battery Distribution Block
J4 connector
J2 Analog
J3 connector
Interconnects to J16 on bus driver module
J2 connector
Interconnects to J12 on bus driver module (5V, 12V, and
24V supervision)