IF 632 Installation and Operation Manual
Release: 3 01/31/01
54
SYSTEM I/O COMPONENTS (600 SERIES)
Conventional
Input Module
The conventional input module (CIM) consists of up to 3 assemblies. The
I/O
Circuit module
, the
Style D (Class A) adapter
, and the
Alarm Display
. To view a
comprehensive listing of compatible devices with the IF650 control panel, refer to
Figure I-2, Compatible Initiation Devices found at the end of this section. Also refer
to Figure I-3, for a comprehensive listing of auxiliary devices.
Circuit
Module
The circuit module provides four (CIM-4) or eight (CIM-8) conventional circuits.
All circuits operate on the Style B (Class B) mode of operation. The
End of Line
Resistor
(EOLR) required is 3.9k ohms with a maximum of 25 ohms line resistance.
Programming jumper (S1) is provided on each board for setting the vertical
position/address of the card (S1-1 through S1-4). The I/O circuit module uses the
lower terminal block and connects via cables to the bus driver module. The
conventional input module and its display require one bay of the IF650 system.
Style "D"
Adapter
The style D adapter card (CIM-SDA) provides 4 or 8 Style D (Class A) circuits to
the I/O circuit module. When the Style D adapter is used the EOLR's are not
required. The style D adapter uses the upper terminal block, and is cabled to the I/O
circuit module.
Display
Module
The display module provides eight (8) red circuit alarm LED's, eight (8) yellow
circuit trouble LED's. Eight (8) circuit tactile switches are provided for
programming
,
Bypass
and
WalkTest
functions. The display module connects (via
the display bus) to the bus driver module. The physical location of the display is set
by the addressing jumper S1. Ensure addressing jumper is set according to its
physical location in the cabinet and matches associated I/O module address jumper
setting. Refer to Figure I-1, Cabinet Module Locations.