9.4.1 Check the water circuit
9.4 Water piping
All piping lengths and distances have been taken into consideration.
Requirements
The maximum allowed thermistor cable length is 20m. This is the maximum allowable distance between the domestic
hot water tank and the unit (only for installations with a domestic hot water tank).The thermistor cable supplied with the
domestic hot water tank is 10m in length.In order to optimize efficiency we recommend installing the 3-way valve and
the domestic hot water tank as close as possible to the unit.
If the installation is equipped with a domestic hot water tank (field supply), please refer to the domestic hot water tank
Installation And Owner's Manual. If there is no glycol (anti-freeze) in the system there is a power supply or pump failure,
drain the system (as shown in the figure below).
NOTE
If water is not removed from the system in freezing weather when unit is not used, the frozen water may damage the
water circle parts.
NOTE
The unit is equipped with a water inlet and water outlet for connection to a water circuit. This circuit must be provided by a
licensed technician and must comply with local laws and regulations.
The unit is only to be used in a closed water system. Application in an open water circuit can lead to excessive corrosion
of the water piping.
Example
:
5
4
4.2
4.1
10
FHL1
FHL2
FHLn
19
20
Indoor
Outdoor
1
15
16
14
12
14
Modbus
16
2
Assembly unit
Code
Assembly unit
Main unit
15
Shut-off valve (Field supply)
User interface(accessory)
Filling valve (Field supply)
Balance tank
Automatic air purge valve
(Field supply)
19
Drainage valve (Field supply)
Collector/distributor (Field supply)
Drainage valve
10
P_o: Outside circulation pump (Field supply)
Expansion vessel(field supply)
12
FHL
1…n
Floor heating loop (Field supply)
Filter (Accessory)
Bypass valve (field supply)
14
16
20
Code
1
2
4
4.1
4.2
5
Installation and operation manual - air-water heat pump Prima
© All rights reserved - Galmet Sp. z o.o. Sp. K.
120
WZÓR
Summary of Contents for Prima
Page 175: ...i 1 Galmet Sp z o o Sp K Prima 175 W Z R...
Page 176: ...3 1 3 1 Prima Galmet Sp z o o Sp K 176 W Z R...
Page 177: ...12 8 3 RCD 30 Galmet Sp z o o Sp K Prima 177 W Z R...
Page 181: ...5 6 EN378 5 CO2 50 CO2 12 24 50 CO2 500 CO2 12 500 CO2 Galmet Sp z o o Sp K Prima 181 W Z R...
Page 195: ...8 10 PCB B PCB B 4 6 PCB A PCB A 9 3 Galmet Sp z o o Sp K Prima 195 W Z R...
Page 206: ...9 4 3 3 3 3 2 60 9 4 4 Prima Galmet Sp z o o Sp K 206 W Z R...
Page 207: ...0 3 98 83 98 83 2 2 0 9 5 2 Galmet Sp z o o Sp K Prima 207 W Z R...
Page 208: ...30 9 7 2 30 0 1 9 7 1 9 6 9 7 B1 13 0 039 30 C 80 20 Prima Galmet Sp z o o Sp K 208 W Z R...
Page 215: ...9 1 9 2 9 1 9 2 9 3 Galmet Sp z o o Sp K Prima 215 W Z R...
Page 224: ...MENU BACK ON OFF UNLOCK C PCB E8 E0 E2 13 4 10 5 1 99 Prima Galmet Sp z o o Sp K 224 W Z R...
Page 235: ...11 11 1 50 11 2 10 5 11 12 10 1 24 9 4 4 pH pH 8 0 pH 7 0 Galmet Sp z o o Sp K Prima 235 W Z R...
Page 247: ...MCE P6 15 15 1 2 3 U V W 4 L1 L2 L3 5 Galmet Sp z o o Sp K Prima 247 W Z R...
Page 249: ...15 1 2 3 4 5 CO2 6 7 8 9 Galmet Sp z o o Sp K Prima 249 W Z R...
Page 250: ...11 12 13 14 25 OFN 15 b 10 Prima Galmet Sp z o o Sp K 250 W Z R...
Page 251: ...17 b c d e g h 80 i j k 18 19 20 16 Galmet Sp z o o Sp K Prima 251 W Z R...
Page 252: ...20 21 Y 4 A Prima Galmet Sp z o o Sp K 252 W Z R...
Page 253: ...XT3 XT3 8 10 4 6 K XT3 Galmet Sp z o o Sp K Prima 253 W Z R...
Page 254: ...XT3 XT3 12 14 16 1 K 40 200 230 12 14 16 3 Prima Galmet Sp z o o Sp K 254 W Z R...