Switch off all power including the unit power supply and backup heater and domestic hot water tank power supply (if
applicable) before removing the switch box service panel.
WARNING
Field wiring guidelines
Most field wiring on the unit is to be made on the terminal block inside the switch box. To gain access to the terminal block,
remove the switch box service panel (door 2).
9.7.3 Precautions on wiring of power supply
Fix all cables using cable ties.
A dedicated power circuit is required for the backup heater.
Installations equipped with a domestic hot water tank (field supply) require a dedicated power circuit for the booster heater.
Please refer to the domestic hot water tank Installation & Owner's Manual. Secure the wiring in the order shown below.
Lay out the electrical wiring so that the front cover does not rise up when doing wiring work and attach the front cover
securely.
Follow the electric wiring diagram for electrical wiring works (the electric wiring diagrams are located on the rear side of door
2.
Install the wires and fix the cover firmly so that the cover may be fit in properly.
9.7.4 Safety device requirment
Use the correct screwdriver to tighten the terminal screws. Small screwdrivers can damage the screw head and prevent
appropriate tightening.
Over-tightening the terminal screws can damage the screws.
Attach a ground fault circuit interrupter and fuse to the power supply line.
In wiring, make certain that prescribed wires are used, carry out complete connections, and fix the wires so that outside force
cannot affect the terminals.
Use a round crimp-style terminal for connection to the power supply terminal board. In case it cannot be used due to
unavoidable reasons, be sure to observe the following instructions.
Do not connect different gauge wires to the same power supply terminal. (Loose connections may cause overheating.)
When connecting wires of the same gauge, connect them according to the figure below.
-
-
1. Select the wire diameters( minimum valve) individually for each unit based on the table 9-1 and table 9-2
,
where the rated
current in table 9-1 means MCA in table 9-2. In case the MCA exceeds 63A, the wire diameters should be selected according
to the national wiring regulation.
2. Maximum allowable voltage range variation between phases is 2%.
3. Select circuit breaker that having a contact separation in all poles not less than 3 mm providing full disconnection
,
where MFA
is used to select the current circuit breakers and residual current operation breakers.
© All rights reserved - Galmet Sp. z o.o. Sp. K.
Installation and operation manual - air-water heat pump Prima
127
WZÓR
Summary of Contents for Prima
Page 175: ...i 1 Galmet Sp z o o Sp K Prima 175 W Z R...
Page 176: ...3 1 3 1 Prima Galmet Sp z o o Sp K 176 W Z R...
Page 177: ...12 8 3 RCD 30 Galmet Sp z o o Sp K Prima 177 W Z R...
Page 181: ...5 6 EN378 5 CO2 50 CO2 12 24 50 CO2 500 CO2 12 500 CO2 Galmet Sp z o o Sp K Prima 181 W Z R...
Page 195: ...8 10 PCB B PCB B 4 6 PCB A PCB A 9 3 Galmet Sp z o o Sp K Prima 195 W Z R...
Page 206: ...9 4 3 3 3 3 2 60 9 4 4 Prima Galmet Sp z o o Sp K 206 W Z R...
Page 207: ...0 3 98 83 98 83 2 2 0 9 5 2 Galmet Sp z o o Sp K Prima 207 W Z R...
Page 208: ...30 9 7 2 30 0 1 9 7 1 9 6 9 7 B1 13 0 039 30 C 80 20 Prima Galmet Sp z o o Sp K 208 W Z R...
Page 215: ...9 1 9 2 9 1 9 2 9 3 Galmet Sp z o o Sp K Prima 215 W Z R...
Page 224: ...MENU BACK ON OFF UNLOCK C PCB E8 E0 E2 13 4 10 5 1 99 Prima Galmet Sp z o o Sp K 224 W Z R...
Page 235: ...11 11 1 50 11 2 10 5 11 12 10 1 24 9 4 4 pH pH 8 0 pH 7 0 Galmet Sp z o o Sp K Prima 235 W Z R...
Page 247: ...MCE P6 15 15 1 2 3 U V W 4 L1 L2 L3 5 Galmet Sp z o o Sp K Prima 247 W Z R...
Page 249: ...15 1 2 3 4 5 CO2 6 7 8 9 Galmet Sp z o o Sp K Prima 249 W Z R...
Page 250: ...11 12 13 14 25 OFN 15 b 10 Prima Galmet Sp z o o Sp K 250 W Z R...
Page 251: ...17 b c d e g h 80 i j k 18 19 20 16 Galmet Sp z o o Sp K Prima 251 W Z R...
Page 252: ...20 21 Y 4 A Prima Galmet Sp z o o Sp K 252 W Z R...
Page 253: ...XT3 XT3 8 10 4 6 K XT3 Galmet Sp z o o Sp K Prima 253 W Z R...
Page 254: ...XT3 XT3 12 14 16 1 K 40 200 230 12 14 16 3 Prima Galmet Sp z o o Sp K 254 W Z R...