9.7.5 Remove the switch box cover
NOTE
Unit
4kW
6kW
8kW
10kW
12kW
14kW
16kW
12kW 3-PH 14kW 3-PH
16kW 3-PH
Maximum
overcurrent
protector(MOP)(A)
18
18
19
19
30
30
30
14
14
14
Wiring size(mm
2
)
4.0
4.0
4.0
4.0
6.0
6.0
6.0
2.5
2.5
2.5
MCA : Max. Circuit Amps. (A)
TOCA : Total Over-current Amps. (A)
MFA : Max. Fuse Amps. (A)
MSC : Max. Starting Amps. (A)
RLA : In nominal cooling or heating test condition
,
the input Amps of compressor where MAX. Hz
can operate Rated Load Amps. (A)
KW : Rated Motor Output
FLA : Full Load Amps. (A)
Unit
8kW
10kW
12kW
14kW
16kW
12kW 3-PH 14kW 3-PH
16kW 3-PH
Maximum
overcurrent
protector(MOP)(A)
32
32
43
43
43
27
27
27
Wiring size(mm
2
)
8.0
8.0
10.0
10.0
10.0
4.0
4.0
4.0
1-phase 8-16kW and 3-phase 12-16kW standard with backup heater 9kW(3-phase)
Unit
4kW
6kW
8kW
10kW
12kW
14kW
16kW
12kW 3-PH 14kW 3-PH
16kW 3-PH
Maximum
overcurrent
protector(MOP)(A)
31
31
32
32
43
43
43
27
27
27
Wiring size(mm
2
)
6.0
6.0
8.0
8.0
10.0
10.0
10.0
4.0
4.0
4.0
1-phase 4-16kW and 3-phase 12-16kW standard with backup heater 3kW (1-phase)
1-phase 4-16kW standard and 3-phase 12-16kW standard
UNIT POWER SUPPLY
1-phase
L
N
L N
LPS
F
USE
UNIT POWER SUPPLY
3-phase
LPS
F
USE
L1
N
L2 L3
L3
N
L2
L1
UNIT POWER SUPPLY
3-phase
LPS
F
USE
L1
N
L2 L3
L3
N
L2
L1
UNIT POWER SUPPLY
1-phase
L N
LPS
F
USE
The ground fault circuit interrupter must be 1 high-speed type of 30mA(<0.1s). Please use 3-core shielded wire.
The default of backup heater is option 3 (for 9kW backup heater). If 3kW or 6kW backup heater is needed, please
ask professional installer to change the Dip switch of S1 to option 1(for 3kW backup heater) or option 2(for 6kW backup
heater), refer to 10.1.1 FUNCTION SETTING.
Stated values are maximum values (see electrical data for exact values).
© All rights reserved - Galmet Sp. z o.o. Sp. K.
Installation and operation manual - air-water heat pump Prima
129
WZÓR
Summary of Contents for Prima
Page 175: ...i 1 Galmet Sp z o o Sp K Prima 175 W Z R...
Page 176: ...3 1 3 1 Prima Galmet Sp z o o Sp K 176 W Z R...
Page 177: ...12 8 3 RCD 30 Galmet Sp z o o Sp K Prima 177 W Z R...
Page 181: ...5 6 EN378 5 CO2 50 CO2 12 24 50 CO2 500 CO2 12 500 CO2 Galmet Sp z o o Sp K Prima 181 W Z R...
Page 195: ...8 10 PCB B PCB B 4 6 PCB A PCB A 9 3 Galmet Sp z o o Sp K Prima 195 W Z R...
Page 206: ...9 4 3 3 3 3 2 60 9 4 4 Prima Galmet Sp z o o Sp K 206 W Z R...
Page 207: ...0 3 98 83 98 83 2 2 0 9 5 2 Galmet Sp z o o Sp K Prima 207 W Z R...
Page 208: ...30 9 7 2 30 0 1 9 7 1 9 6 9 7 B1 13 0 039 30 C 80 20 Prima Galmet Sp z o o Sp K 208 W Z R...
Page 215: ...9 1 9 2 9 1 9 2 9 3 Galmet Sp z o o Sp K Prima 215 W Z R...
Page 224: ...MENU BACK ON OFF UNLOCK C PCB E8 E0 E2 13 4 10 5 1 99 Prima Galmet Sp z o o Sp K 224 W Z R...
Page 235: ...11 11 1 50 11 2 10 5 11 12 10 1 24 9 4 4 pH pH 8 0 pH 7 0 Galmet Sp z o o Sp K Prima 235 W Z R...
Page 247: ...MCE P6 15 15 1 2 3 U V W 4 L1 L2 L3 5 Galmet Sp z o o Sp K Prima 247 W Z R...
Page 249: ...15 1 2 3 4 5 CO2 6 7 8 9 Galmet Sp z o o Sp K Prima 249 W Z R...
Page 250: ...11 12 13 14 25 OFN 15 b 10 Prima Galmet Sp z o o Sp K 250 W Z R...
Page 251: ...17 b c d e g h 80 i j k 18 19 20 16 Galmet Sp z o o Sp K Prima 251 W Z R...
Page 252: ...20 21 Y 4 A Prima Galmet Sp z o o Sp K 252 W Z R...
Page 253: ...XT3 XT3 8 10 4 6 K XT3 Galmet Sp z o o Sp K Prima 253 W Z R...
Page 254: ...XT3 XT3 12 14 16 1 K 40 200 230 12 14 16 3 Prima Galmet Sp z o o Sp K 254 W Z R...