Symptom 8: DHW mode can’t change to Heat mode immediately
POSSIBLE CAUSES
CORRECTIVE ACTION
Heat exchanger for space
heating not big enough
Space heating load is small
When the ambient temperature is
low, the hot water is not enough
and the AHS is not operated or
operated late
DHW mode priority
Manual turn on the FAST WATER
function, after the hot water meets
the requirements, the heat pump
fails to switch to the air-conditioning
mode in time when the air
conditioner is in demand
Disinfect function is
enabled but without TBH
Normal , no need for heating
Manual turn off the FAST WATER function
If there is AHS or IBH connect to the unit, when the outdoor unit failed, the
hydraulic module board must run DHW mode till the water temperature
reach the setting temperature before change to heating mode.
• Disable disinfect function
• add TBH or AHS for DHW mode
• Set "T4DHWMIN", the suggested valve is ≥
-5
℃
• Set "T4_TBH_ON", the suggested valve is ≥
5
℃
• Set "t_DHWHP_MAX" to minimum valve, the suggested valve is
60min.
• If circulating pump out of unit is not controlled by unit, try to
connect it to the unit.
• Add 3-way valve at the inlet of fan coil to ensure enough water
flow.
Symptom 9: DHW mode heat pump stop work but setpoint not reached, space heating require heat but unit stay in DHW mode
POSSIBLE CAUSES
CORRECTIVE ACTION
Surface of coil in the tank
not large enough
The same solution for Symptom 7
TBH or AHS not available
Heat pump will stay in DHW mode untill "t_DHWHP_MAX" reached or
setpoint is reached. Add TBH or AHS for DHW mode,TBH and AHS should
be controlled by the unit.
13.3 Operation parameter
This menu is for installer or service engineer reviewing the operation parameters.
At home page, go to ''MENU''>''OPERATION PARAMETER''.
Press ''OK''. There are nine pages for the operating parameter as following. Press ''
▼
''
、
''
▲
'' to scroll.
Press"►" and "◄" to check slave units' operation parameter in cascade system. The address code in the upper right corner
00
will change from "#00" to "#01"
、
"#02" etc. accordingly
OPERATION PARAMETER
#00
OPERATE MODE
COOL
ADDRESS
SV1 STATE
ON
ONLINE UNITS NUMBER
1
SV2 STATE
OFF
SV3 STATE
OFF
PUMP_I
ON
1/9
OPERATION PARAMETER
#00
PUMP-C
OFF
ADDRESS
PUMP-S
OFF
PUMP-O
OFF
PUMP-D
OFF
PIPE BACKUP HEATER
OFF
TANK BACKUP HEATER
ON
2/9
OPERATION PARAMETER
#00
T1 LEAVING WATER TEMP. 35°C
ADDRESS
WATER FLOW
1.72m
3
/h
GAS BOILER
OFF
HEAT PUMP CAPACTIY 11.52kW
POWER CONSUM.
1000kWh
Ta ROOM TEMP
25°C
3/9
OPERATION PARAMETER
#00
Tw2 CIRCUIT2 WATER TEMP. 35°C
ADDRESS
TIS’ C1 CLI. CURVE TEMP. 35°C
T5 WATER TANK TEMP.
53°C
TIS2’ C2 CLI. CURVE TEMP. 35°C
TW_O PLATE W-OUTLET TEMP. 35°C
TW_I PLATE W-OUTLET TEMP. 30°C
4/9
OPERATION PARAMETER
#00
Tbt2 BUFFERTANK_LOW TEMP. 35°C
ADDRESS
IDU SOFTWARE 01-09-2019V01
Tbt1 BUFFERTANK_UP TEMP. 35°C
5/9
Tsolar
25°C
OPERATION PARAMETER
#00
COMP.CURRENT
12A
ADDRESS
COMP.FREQENCY
24Hz
ODU MODEL
6kW
COMP.RUN TIME
54 MIN
COMP.TOTAL RUN TIME 1000Hrs
EXPANSION VALVE
200P
6/9
© All rights reserved - Galmet Sp. z o.o. Sp. K.
Installation and operation manual - air-water heat pump Prima
155
WZÓR
Summary of Contents for Prima
Page 175: ...i 1 Galmet Sp z o o Sp K Prima 175 W Z R...
Page 176: ...3 1 3 1 Prima Galmet Sp z o o Sp K 176 W Z R...
Page 177: ...12 8 3 RCD 30 Galmet Sp z o o Sp K Prima 177 W Z R...
Page 181: ...5 6 EN378 5 CO2 50 CO2 12 24 50 CO2 500 CO2 12 500 CO2 Galmet Sp z o o Sp K Prima 181 W Z R...
Page 195: ...8 10 PCB B PCB B 4 6 PCB A PCB A 9 3 Galmet Sp z o o Sp K Prima 195 W Z R...
Page 206: ...9 4 3 3 3 3 2 60 9 4 4 Prima Galmet Sp z o o Sp K 206 W Z R...
Page 207: ...0 3 98 83 98 83 2 2 0 9 5 2 Galmet Sp z o o Sp K Prima 207 W Z R...
Page 208: ...30 9 7 2 30 0 1 9 7 1 9 6 9 7 B1 13 0 039 30 C 80 20 Prima Galmet Sp z o o Sp K 208 W Z R...
Page 215: ...9 1 9 2 9 1 9 2 9 3 Galmet Sp z o o Sp K Prima 215 W Z R...
Page 224: ...MENU BACK ON OFF UNLOCK C PCB E8 E0 E2 13 4 10 5 1 99 Prima Galmet Sp z o o Sp K 224 W Z R...
Page 235: ...11 11 1 50 11 2 10 5 11 12 10 1 24 9 4 4 pH pH 8 0 pH 7 0 Galmet Sp z o o Sp K Prima 235 W Z R...
Page 247: ...MCE P6 15 15 1 2 3 U V W 4 L1 L2 L3 5 Galmet Sp z o o Sp K Prima 247 W Z R...
Page 249: ...15 1 2 3 4 5 CO2 6 7 8 9 Galmet Sp z o o Sp K Prima 249 W Z R...
Page 250: ...11 12 13 14 25 OFN 15 b 10 Prima Galmet Sp z o o Sp K 250 W Z R...
Page 251: ...17 b c d e g h 80 i j k 18 19 20 16 Galmet Sp z o o Sp K Prima 251 W Z R...
Page 252: ...20 21 Y 4 A Prima Galmet Sp z o o Sp K 252 W Z R...
Page 253: ...XT3 XT3 8 10 4 6 K XT3 Galmet Sp z o o Sp K Prima 253 W Z R...
Page 254: ...XT3 XT3 12 14 16 1 K 40 200 230 12 14 16 3 Prima Galmet Sp z o o Sp K 254 W Z R...