Questions? Please Contact Your Local Manufacturer’s Representative
SECTION 3
VSRT-IOM-2022-0728
OPERATION
3-19
Par. No.
Parameter
Min Value
Max Value
Fulton Setting
Customer
602
Actuator’s direction of rotation
Index 0 = fuel, Index 1 = air
0 = counterclockwise
1 = clockwise
0
1
0
0
606
Tolerance limit of position monitoring
0.5
2.5
1.7
641
Control of speed standardization of VSD
-25
1
0
642
Standardized speed
Index 0 = uC1
Index 1 = uC2
650
6500
Undefined
645
Configuration of analog output
0 = DC 0…10 V
1 = DC 2…10 V
2 = DC 0/2…10 V
0
2
0
700
Error History
701
Error history: 701-725.01. Code
0
255
.
Error history: 701-725.02. Diagnostic Code
0
255
.
Error history: 701-725.03. Error class
0
6
.
Error history: 701-725.04. Phase
0
255
.
Error history: 701-725.05. Startup counter
0
99999999
725
Error history: 701-725.06. Load
0 %
100 %
900
Process Data
903
Current output
Index 0 = fuel
Index 1 = air
0 %
100 %
0
922
Incremental position of actuators
Index 0 = fuel
Index 1 = air
-50
150
0
935
Absolute speed
0
65535
0
936
Standardized speed
-200 %
200 %
942
Active load source
0
255
947
Result of contact sensing (bit-coded)
0
255
950
Required relay state (bit-coded)
0
255
954
Intensity of flame
0 %
100 %
960
Actual flow rate
0
65525
961
Status for external modules and display
0
255
981
Error storage: Code
0
255
982
Error storage: Diagnostic code
0
255
992
Error flags
0
0xFFFFFFFF
TABLE 8
- STEAM PROGRAM FOR SIEMENS LMV3*
*Data is for reference purposes only. Fulton Companies is not responsible for this product, including (but not limited to) its accuracy, reliability, and
safety. No Fulton document should substitute for full review of documentation available from the product manufacturer.
+Out of Test Fire
Note:
Customer settings should be recorded in the Customer column for reference.