5-11
VERTICAL STEAM BOILER
ANNUAL MAINTENANCE CHECKLIST
DATE
TECHNICIAN
TECH. COMPANY
TECH CERTIFICATE #
BOILER MODEL
NATIONAL BOARD #
NOTE:
TO BE COMPLETED BY A FACTORY AUTHORIZED TECHNICIAN HOLDING A VALID STEAM BOILER CERTIFICATE OF REGISTRATION.
ANNUAL MAINTENANCE:
Burner head removed and visually inspected
Burner head cleaned (30-72.5 psi air only)
Burner head reinstalled with new gaskets
Burner flange hardware torqued to spec (see Section 4 of IOM)
Low water probe(s) removed and replaced. Floats opened and cleaned
Combustion air inlet filter replaced with new, cyclone bucket cleaned
Direct spark ignition replaced with new (where applicable)
Oxygen sensor replaced with new, Reset O2, and Set Initial O2 performed
PURE Control software/firmware update installed (where directed)
Special gas vent system and condensate drains inspected
Combustion air intake inspected
Safety relief valve inspected, replace if necessary
Flexible premix couplings inspected, replace immediately if worn
(fill in tables on reserve side)
Open factory Service Bulletin(s) addressed (where applicable)
COMPLETE
COMPLETE
COMPLETE
COMPLETE
COMPLETE
COMPLETE
COMPLETE
COMPLETE
COMPLETE
COMPLETE
COMPLETE
COMPLETE
COMPLETE
COMPLETE
(fill in tables below)
Combustion verification completed, adjust as necessary
Safety checks table completed
Waterside inspection, hand hole gaskets replaced
CLEAN
NEEDS TO BE CLEANED
WATER CHEMISTRY: Verify water chemistry is within specific limits, correct where required.
pH (8.5-10.5)
Oxygen (None Detected)
Iron/Copper (<.01 ppm)
Total Alkalinity (<300 ppm)
Hardness (<110 ppm)
ppb
ppm
ppm
ppm
Total Dissolved Solids (<2000ppm)
ppm
OH Alkalinity (200-300 ppm)
ppm
Suspended Solids (No visible tubidity)
Total Organic Carbon (No sheen, no foam)
Conductivity (<2985 mS/cm)
mS/cm
Visual Oil (None Detected)
SAFETY CHECKS:
Check all safeties below for proper operation and document the final settings.
DEVICE
SETTING
OPERATIONAL
Low Water Safety
Air Switch
Low Gas Pressure Switch
High Gas Pressure Switch
Water Level Control
High Pressure Limit
Blower Leak Test
Pressure Controller
Proof of Closure (POC)
Fuel Train Leak Test
Air Filter Switch
DEVICE
SETTING
ERATIONAL
OP
Secondary Low Water
NOT APPLICABLE
NOT APPLICABLE
NOT APPLICABLE
NOT APPLICABLE
NOT APPLICABLE
NOT APPLICABLE
NOT APPLICABLE
NOT APPLICABLE
NOT APPLICABLE
NOT APPLICABLE
NOT APPLICABLE
NOT APPLICABLE
NOT APPLICABLE
NOT APPLICABLE