SECTION 3
VSRT-IOM-2022-0728
OPERATION
3-17
Par. No.
Parameter
Min Value
Max Value
Fulton Setting
Customer
208
Program stop
0 = deactivated
1 = PrePurgP (Ph24)
2 = IgnitPos (Ph36)
3 = interval 1 (Ph44)
4 = interval 2 (ph52)
0
4
0
210
Alarm in the event of start prevention
0 = deactivated
1 = activated
0
1
0
211
Fan ramp up time
2
s
60 s
5 s
212
Max time down to lo
w fire
0.2
s
10 min
30 s
10 s
213
Min time home run
2 s
60 s
2
s
214
Max time start release
0.2
s
10 min
20 s
215
Repetition limit safety loop
1
16
1
217
Max time to detector signal
5
s
10 min
30 s
221
Gas: Active detector flame evaluation
0 = QRB / QRC
1 = ION / QRA
0
1
1
222
Gas: Pre-purging
0 = deactivated
1 = activated
0
1
1
223
Repetition limit pressure switch mini-gas
1
16
1
225
Gas: Pre-purge time
20 s
60 s
30 s
226
Gas: Pre-ignition time
0.2 s
60 min
2 s
227
Gas: Safety time 1 (TSA1)
0.2 s
10 s
5 s
229
Gas: time to respond to pressure faults in TSA1
0.2 s
9.8 s
1.8 s
230
Gas: Interval 1
0.2 s
60 s
5 s
231
Gas: Safety time 2 (TSA2)
0.2 s
10 s
5 s
232
Gas: Interval 2
0.2 s
60 s
2.0 s
233
Gas: Afterburn time
0.2 s
60 s
8 s
234
Gas: Post purge time
0.2 s
108 mi,
15 s
237
Gas pressure switch-max / POC input
0 = deactivated
1 = pressure switch-max
2 = POC
1
2
2
239
Gas: Forced intermittent operation
0 = deactivated
1 = activated
0
1
1
240
Gas: Repetition limit loss of flame
1
2
1
*Data is for reference purposes only. Fulton Companies is not responsible for this product, including (but not limited to) its accuracy, reliability, and safety. No
Fulton document should substitute for full review of documentation available from the product manufacturer.
+Out of Test Fire
Note:
Customer settings should be recorded in the Customer column for reference.
TABLE 8
- STEAM PROGRAM FOR SIEMENS LMV3*