OPERATION
VSRT-IOM-2022-0728
SECTION 3
3-18
*Data is for reference purposes only. Fulton Companies is not responsible for this product, including (but not limited to) its accuracy, reliability, and safety. No
Fulton document should substitute for full review of documentation available from the product manufacturer.
+Out of Test Fire
Note:
Customer settings should be recorded in the Customer column for reference.
TABLE 8
- STEAM PROGRAM FOR SIEMENS LMV3*
Par. No.
Parameter
Min Value
Max Value
Fulton Setting
Customer
241
Gas: Execution leakage test
0 = no leakage test
1 = leakage test on start up
2 = leakage test on shut down
3 = leakage test on both
0
3
0
242
Gas: Leakage test evacuation time
0.2 s
10s
3 s
243
Gas: Leakage test time atm pressure
0.2 s
60 s
10 s
244
Gas: Leakage t
est filling time
0.2 s
10s
3 s
245
Gas: Leakage test time gas pressure
0.2 s
60 s
10 s
246
Gas: Waiting time gas shortage
0.2 s
60 s
10 s
400
Ratio Curves
401
Ratio control curve fuel actuator
0
90
402
Ratio control curve air actuator
0
90
403
Ratio control curve VSD
20 %
100 %
500
Ratio Control
501
No-flame positions fuel actuator
Index 0 = no-load position
Index 1 = pre-purge position
Index 2 = post-purge position
0
90
0
0
0
502
No-flame positions air actuator
Index 0 = no-load position
Index 1 = pre-purge position
Index 2 = post-purge position
0
90
0
65
45
503
No-flame speeds VSD
Index 0 = no-load position
Index 1 = pre-purge position
Index 2 = post-purge position
0 %
100 %
0
65 %
65 %
522
Ramp up
5 s
20 s
20 s
523
Ramp down
5 s
20 s
20 s
542
Activation of VSD / PWM fan
0
1
1
544
Modulation Ramp
32 s
80 s
32 s
545
Lower load limit
20 %
100 %
20%
546
Upper load limit
20 %
100 %
100%
600
Actuators