Maintenance (integrated DHW models)
6 1
Emptying the hydraulic unit
- Remove the facade from the hydraulic unit
- Place the distribution valve in the middle position
- Open the emptying valve (ref 5)
- Open the hydraulic unit’s manual bleed-tap (ref 6)
- Open the installation bleed tap
6 2
Distribution valve
Carefully comply with the direction for fitting the
distribution valve:
Channel AB: Inlet from the hydraulic unit (heat pump)
Channel A Open: Outlet to DHW tank
Channel B Open: Outlet to the heating circuit
6 3
ACI check
- Check polarity
- Check voltage: The appliance powered on, the voltage
value must be positive and lie between 0 + and + 6 5 V
dc
Heating
return
Valve
Outlet to
Exchanger
Outlet to DHW tank
Valve motor
figure 6 - Fitting the distribution valve
figure 7 - ACI check
Check ACI voltage
Connecting
ACI connecting:
The – on the tank mass
The + on the electrode connector
Maintenance document "1792 - EN"