Eco
Line N°
Programming line
912
Cooling limit at OT
913
Lock time after end of heating
Cooling limit at OT
If the composite outdoor temperature is higher than the
cooling limit, cooling is released If the composite outdoor
temperature falls at least 0 5°C below the cooling limit,
cooling is locked
Lock time after end of heating
To avoid a quick start of cooling after termination of
heating, the cooling function is locked for a time period
which can be adjusted with this setting The lock time
starts when there is no valid heating demand from
heating circuit 1 Heating demands from heating circuits
2 or P are ignored
Information:
Switching off and switching on again the mode selection
key causes the lock time to be interrupted
Summer Compensation
Line N°
Programming line
918
Summer comp start at OT
919
Summer comp end at OT
920
Summer comp setp increase
In summer the "cooling comfort setpoint" (902) is gradually
increased according to the outdoor temperature This
saves on cooling power and prevents the differences
between the ambient temperature of the room and the
outdoor temperature being too high
The resulting "room temperature setpoint" (cooling) can
be viewed in the Info section
Summer compensation start at OT
Summer compensation starts to be active from the
outdoor temperature defined here If the outdoor
temperature continues to rise, the comfort setpoint will
be gradually increased
Summer compensation end at OT
At this outdoor temperature the summer compensation
reaches its peak efficiency (920) If the outdoor
temperature continues to rise, it will no longer influence
the comfort setpoint
Summer compensation setpoint increase
This setting defines the highest value to which the comfort
setpoint can be increased
Flow Setpoint Limitation
LINE N° PROGRAMMING LINE
923 Flow temp setp min at OT 25°C
924 Flow temp setp min at OT 35°C
It is possible to assign a lower limit to the cooling flow
temperature. The limitation line will be defined by two
reference points. In addition the resulting flow setpoint
will have a lower limit and may not be less than 5 °C
Flow temp setp min at OT 25°C
Determines the lowest flow temperature for a composite
outdoor temperature of 25°C
Flow temp setp min at OT 35°C
Determines the lowest flow temperature for a composite
outdoor temperature of 35°C
Warning:
If no outdoor temperature is available, the controller will
use the "Min. flow setpoint at OT= 35°C" parameter.
902
920
924
923
Maintenance document "1792 - EN"
- 71 -
Split system single phase type